Specifications
Classic Circular 36"/54" Washfountain with Touch Time™ Control
WF2605, WF2608 Terrazzo – WF2705, WF2708 Stainless Steel Installation Instructions
6 4/6/2007 Bradley Corporation • 215-1518 Rev. C; EN 06-915B
Rough-In Specifications continued . . .
Type H
Centrally rising vent with
supplies from below
Type O
Off-line vent with
supplies from above
TOP VIEW
TOP VIEW
NOTE: UPC and IPC restrict the vertical
distance from the fixture outlet to the trap
weir to not more than 24". Check state and
local codes for variances.
Rough-In Notes For All Models:
1. All pipes and fittings not furnished by
Bradley are shown in broken lines.
2. Supply lines for one to two washfountains should
be 1"; for three washfountains 1-1/4"; for more
than three washfountains, pipe sizes should be
increased proportionately.
3. Overhead supplies must be reduced to 1/2"
copper tube to pass through support tube.
4. Check valve inlets are 1/2" NPT.
5. Dimensions shown in parentheses are millimeters.
Remote mounting of transformer with 24 VAC electrical
supply to washfountain is recommended (this conduit
location is only a recommendation). See local electrical
codes before roughing in.
1" NPT SUPPLIES FROM ABOVE MUST
REDUCE TO 1/2 NOM. COPPER TUBE
ON THESE CENTERS TO PASS
THRU WASHFOUNTAIN
7/8"
(22.2)
7/8"
(22.2)
HOT
1-1/4"
(32)
4"
(102)
2" NPT DRAIN:
STUB UP 3" (76)
ABOVE FLOOR
54" (1372) BOWL
36" (914) BOWL
COLD
5"
(127)
CONDUIT
LOCATION
*
1" NPT SUPPLIES THROUGH
FLOOR: STUB UP 2-1/2" (64)
ABOVE FLOOR
1-1/2" NPT
VENT TO
CEILING
36" (914) BOWL
54" (1372) BOWL
7-5/8"
(194)
7-5/8"
(194)
COLD
HOT
2" NPT DRAIN:
STUB UP 3"
(76) ABOVE
FLOOR
4"
(
102)
2-1/2"
(
64)
5"
(127)
CONDUIT
LOCATION
*
*