Specifications

Classic Circular 36"/54" Washfountain with Infrared Control
Installation Instructions WF2605, WF2608 Terrazzo — WF2705, WF2708 Stainless Steel
5Bradley Corporation • 215-1449 Rev. D; EN 06-915B 4/6/2007
Rough-In Notes For All Models:
1. All pipes and fittings not furnished by
Bradley are shown in broken lines.
2. Supply lines for one to two washfountains should
be 1"; for three washfountains 1-1/4"; for more
than three washfountains, pipe sizes should be
increased proportionately.
3. Overhead supplies must be reduced to 1/2"
copper tube to pass through support tube.
4. Check valve inlets are 1/2" NPT.
5. Dimensions shown in parentheses are millimeters.
Remote mounting of transformer with 24 VAC electrical
supply to washfountain is recommended (this conduit
location is only a recommendation). See local electrical
codes before roughing in.
*
Type A
Off-line vent with
supplies from below
Type B
Centrally rising vent with
supplies from above
TOP VIEW
1" NPT SUPPLIES THROUGH
FLOOR: STUB UP 2-1/2" (64)
ABOVE FLOOR
7-5/8"
(194)
7-5/8"
(194)
COLD
HOT
4"
(102)
2-1/2"
(64)
2" NPT DRAIN:
STUB UP 3" (76)
ABOVE FLOOR
36" (914) BOWL
54" (1372) BOWL
5"
CONDUIT
LOCATION
*
1" NPT SUPPLIES FROM ABOVE
MUST REDUCE TO 1/2 NOM.
COPPER TUBE ON THESE CENTERS
TO PASS THRU WASHFOUNTAIN
7/8"
(22.2)
7/8"
(22.2)
COLD
HOT
1-1/2" NPT VENT
TO CEILING
2" NPT DRAIN:
STUB UP 3" (76)
ABOVE FLOOR
4"
(102)
36" (914) BOWL
54" (1372) BOWL
1-1/4
"
(32)
5"
(127)
CONDUIT
LOCATION
*
TOP VIEW
NOTE: UPC and IPC restrict the vertical
distance from the fixture outlet to the trap
weir to not more than 24". Check state and
local codes for variances.
Rough-In Specifications