Installation manual
Installation SS-2N/AST/STD, SS-2N/AST/WH
Bradley Corporation • 215-1498 Rev. F; ECM 11-08-011 10/24/11 13
Tempered Line Adapter Option
Part no. S39-804
(replaces S59-4000 if tempered line
is used)
Strainer
(173-028)
Problem Cause Solution
External
leaks.
Damaged cartridge or O-rings. Replacecartridgewithpartnumber269-1927
Improper water
temperature or
temperature
fluctuation.
Hot water supply is not 10° above desired set point. Increase hot water supply temperature
Valve temperature is not properly set. Adjustthetemperatureasshownonpage10,step8.
Limited water
flow.
Dirt and debris have built up in the valve or strainer. 1.Checktomakesurebothhotandcoldsuppliesare
connected to the Navigator mixing valve and that they
have water flow.
2. Remove cover and U-clip. Remove the cartridge and
clean the strainer. It is not required to grease cartridge,
however if desired, use silicone grease only. Do not use
greaseoncheckvalves.
Parts List
Item Part No. Description
Quantity
S59-4000 S59-4000A S59-4000BY
1 160-463 Cap Screw 1 1 1
2 107-582 Cover 1 1 1
3 269-1927 Thermostatic Cartridge 1 1 1
4 198-014 CheckValve* 2 2 2
5 132-051 RetainingRing* 2 2 2
6 118-319 Valve Body 1 1 1
7 146-079 U-Clip 1 1 1
*IncludedwithPrepackS65-326
1
2
3
4
5
4
5
7
6
Thermostatic Mixing Valve Troubleshooting
Before attempting to troubleshoot the valve or disassemble the components, check for the following conditions:
• Ifstopvalvesareused,makesurethattheyarefullyopen.
• Makesurethatthehotandcoldinletpipesareconnectedproperly,andthattherearenocross-connectionsor
leaking stop valves.
• Checkthehotwaterheateroutputtomakesurethatitisatleast10°Fabovethesettemperature.
Be sure to close the appropriate shut-off valves prior to disassembly of the valve and reopen the valves after inspection and
repair is complete.