Installation manual

Express
®
Deck Lavatory System EXD-Series
Installation EXD-2N
Bradley Corporation • 215-1542 Rev. F; ECN 11-08-011 3/2/2012 13
Tempered Line Adapter Option
Part no. S39-804
(replaces S59-4000 if tempered line
is used)
Strainer
(173-028)
Problem Cause Solution
External leaks.
Damaged cartridge or O-rings. Replacecartridgewithpartnumber269-1927
Improper water
temperature or
temperature
fluctuation.
Hot water supply is not 10° above desired set
point.
Increasehotwatersupplytemperature
Valve temperature is not properly set. Adjustthetemperatureasshownonpage10,step7.
Limited water
flow.
Dirt and debris have built up in the valve or
strainer.
1.Checktomakesurebothhotandcoldsupplies
are connected to the Navigator mixing valve and that
theyhavewaterflow.
2. Remove cover and U-clip. Remove the cartridge
andcleanthestrainer.Itisnotrequiredtogrease
cartridge,howeverifdesired,usesiliconegrease
only.Donotusegreaseoncheckvalves.
Parts List
Item Part No. Description
Quantity
S59-4000 S59-4000A S59-4000BY
1 160-463 CapScrew 1 1 1
2 107-582 Cover 1 1 1
3 269-
1927
Thermostatic Cartridge 1 1 1
4 198-014 CheckValve* 2 2 2
5 132-051 RetainingRing* 2 2 2
6 118-319 Valve Body 1 1 1
7 146-079 U-Clip 1 1 1
*IncludedwithPrepackS65-326
1
2
3
4
5
4
5
7
6
Thermostatic Mixing Valve Troubleshooting
Before attempting to troubleshoot the valve or disassemble the components, check for
the following conditions:
• Ifstopvalvesareused,makesurethattheyarefullyopen.
• Makesurethatthehotandcoldinletpipesareconnectedproperly,andthatthereare
no cross-connections or leaking stop valves.
• Checkthehotwaterheateroutputtomakesurethatitisatleast10°Fabovetheset
temperature.
Be sure to close the appropriate shut-off valves prior to disassembly of the valve and reopen
the valves after inspection and repair is complete.