Service Manual
Anode inspection and replacement
Step 1. Position main power switch to “OFF”
Step 2. Disconnect (unplug) water heater from 120
volt power source.
Step 3. Turn off water supply and
drain water heater.
Step 4. Locate (see photo below) and remove anode rods from heater (1-1/16 hex socket). U65L has 3 anodes (2
front and 1
side) and U100L 5 anodes (3 front and 2 side).
Step 5. Visually inspect anode rod. Anode rod should show signs of depletion,
this is normal. If
the depletion is ½ of the original diameter (approximately ¾" diameter), replacement is
recommended. If any of the s
teel core of the anode is exposed, replacement is
recommended.
Step 6. Upon completion of inspection or subsequent replacement, apply thread sea
ling tape or other
thread compound to threads of anode and reinstall into heater. Restore water supply
and check for and repair any leaks found.
Ste
p 7. Restore 120 volts to water heater and verify proper heater operation following the
instructions on the lighting instruction label or the l
ighting instruction located in the
installation and operating instruction manual.
WARNING
Heater components and stored water may be HOT when performing the following steps in
this procedure. Take necessary precaution to prevent personal injury.
45
Front of water heater.
Anodes located under
plastic covers between
inlet and outlet water
connections.
Side of water heater. Anodes
located under plastic covers
behind the circulator assembly.
Circulator will need to be
disconnected to get to anodes
locations. R
efer to circulator
assembly replacement procedure.
45