Service Manual

For models with Honeywell Integrated Control
System w/ Direct Spark Ignition
Thermostat calls for heat.
Combustion blower & circulator start while the damper opens.
Blower pre-purge period of 30 seconds.
Trial for Ignition. (5 seconds, 3 trials).
Flame establishing period (3 seconds), gas valve opens, sparks from spark rod to burner surface to ignite
the gas.
Burner on, flame proving period (2 seconds). Requires a minimum of 0.8 microamp through flame sense
rod to prove flame.
If either blocked vent safety switch contacts (normally closed) or circulator flow switch and damper contacts
(normally open) remain open after being energized, then the ignition sequence will not start and an error
code 29 (Safety switch circuit failed to close
or open) will be shown on the display.
Steady State Operation: Burner continues to operate until:
Thermostat circuit opens, gas valve closes, blower continues to operate for 30 second post-purge period.
If the normally closed blocked vent safety switch opens, the gas valve closes, the blower post-purges, then
shuts off with error code 26 displayed in a lockout condition.
Thermostat satisfied.
Gas valve closes, burner extinguished.
Blower post purge for
30 seconds.