Installation / Operation Instruction Manual
11
SECTION III
GENERAL INFORMATION
FEATURES
This water heater contains the following features:
HEAT EXCHANGER -- The heat exchanger (coil) has 3/4” NPT
female fittings.
These water heaters with stainless steel single-wall heat
exchangers meet the Uniform Plumbing Code for installation
in all potable water systems provided that:
• The boiler water (including additives) is practically non-
toxic, having toxicity rating of class of 1 as listed in
Clinical Toxicology of Commercial Products.
• The boiler water pressure is limited to maximum 30 psig
by approved relief valve.
• The heat transfer medium is potable water or contains
only substances that are recognized as safe by the U.S.
Food and Drug Administration (FDA).
• The pressure of the heat transfer medium is maintained
less than the normal minimum operating pressure of the
potable water system.
ADJUSTABLE THERMOSTAT – The temperature may be
adjusted from approximately 80°F (27°C) to approximately
160°F(72°C). The aquastat (thermostat) is factory set at
120°F(49°C). It is recommended that lower temperatures be
used to avoid the risk of scalding. Refer to the Section VII of
this manual. It is further recommended, in all cases, that the
water temperature be set for the lowest temperature that
satisfies your hot water needs. This will also provide the most
energy efficient operation of the water heater and minimizes
scale formation.
Setting the water heater temperature at 120°F(49°C) will
reduce the risk of scalds. Some locations require settings to
specific lower temperatures.