Installation / Operation Instruction Manual
16
Pre-installation continued-
Recommended Service Clearances
Non-Piping Side
Front (Aquastat)
Rear
Top
6”(15.2cm)
30”(76.2cm)
1”(2.5cm)
12”(30.5cm)
Table 6: Service Clearances
Appliance Location
1. Boiler Location – Locate the indirect-fired water heater as close
to the boiler as practical.
2. Fixture Locations – For fastest delivery of hot water, place the
indirect-fired water heater close to points of use.
Additional Recommended Components
1. Shut-off Valves – Allows isolation of water heater from domestic
water system and/or boiler system during service.
2. Unions – Allows water heater movement during service if
adequate clearance cannot be provided.
3. Thermal Expansion Tank – If the water heater is installed in a
closed water supply system, such as one having a back-flow
preventer in the cold water line, provide thermal expansion control.
Contact the water supplier or local plumbing inspector for
additional information.
MOVE THE WATER HEATER TO A PERMANENT POSITION BY
SLIDING OR WALKING.
CAUTION
DO NOT drop water heater. DO NOT bump water heater jacket
against floor.
WARNING
DO NOT plug the inlet and outlet tappings of tankless heater left
installed in the boiler.
NOTICE
Note: Per Section 507.2 Seismic Provisions of the 2021 Uniform
Plumbing Code (UPC). Water heaters shall be anchored or strapped
to resist horizontal displacement due to earthquake motion. Strapping
shall be at points within the upper one-third and lower one-third of its
vertical dimensions. At the lower point, a distance of not less than 4
inches shall be maintained from the controls with the strapping.
Please refer to the local authority having jurisdiction to see if there are
any additional local requirements regarding seismic provisions.