Installation / Operation Instruction Manual

14
Pre-installation continued-
IMPORTANT DECISIONS REQUIRED BEFORE INSTALLATION
SIZING
1. Boiler DOE Heating Capacity The indirect-fired water
heater will provide the rated performance only if used in
conjunction with a heat source with a DOE heating capacity
(Heat Output) at least as much as the minimum noted in
Table 3. If the heat source has less capacity, the output of the
tank will be reduced. To determine the approximate reduction
in output from the tank use the following formula:
New Rating = (maximum continuous draw rating) x
Actual Output of Heat Source
Minimum Output of Heat Source
For example, what would the continuous draw rating be if a 50-
gallon indirect-fired water heater were installed with a heat
source having a DOE heating capacity of 85,000 BTU/h?
Answer:
New Rating
= 229 gal/hr x (85,000 BTU/h)/(145,000 BTU/h)
= 229 gal/hr x 0.586 = 134 gal/hr
NOTICE
Increasing the boiler DOE heating capacity above the values listed in
Table 3 will not increase the rating of the water heater.
2. Circulator Sizing Refer to Table 5 for the corresponding
pressure drop through the coil for the given model. Calculate the
pressure drop of all straight pipe and fittings on the supply and
return of the water heater at the selected flow rate. Add the
piping/fitting pressure drop to the pressure drop through the
water heater coil.
Select a circulator that will provide an appropriate flow rate at the
combined pressure drop.
SYSTEM ZONE CONTROL
The indirect-fired water heater must be installed as a zone separate
from the space heating system. The domestic hot water zone’s piping
and circulator must be sized for a minimum flow rate with all zones in
use and a maximum flow rate with only the water heater in use. For
this reason, the preferred method of zone control is with circulators.
1. Circulators With space heating zones using circulators, the
indirect-fired heater should be added as an additional zone with
a circulator.