Figure 2 – Water Heater Illustration and Label Placement Diagram
*In models with a single heating element, the element is replaced with a plug.
INDIRECT WATER HEATER RATINGS
Table 1: Indirect Water Heater Performance in Boiler Application
MODEL
Maximum First Hour
Rating (Gal/Hr) @
140 °F 115 °F
Continuous Draw
Rating (Gal/Min) @
140 °F 115 °F
Approximate Boiler Output
Needed For Ratings
(BTU/hr)
Single-wall 60-Gallon
306 456 4.2 6.7 220,000
Double-wall 60-Gallon 210 305 2.6 4.2 140,000
Single-wall 75-Gallon
321 470 4.2 6.7 220,000
Double-wall 75-Gallon 225 320 2.6 4.2 140,000
Single-wall 115-Gallon
357 507 4.2 6.7 220,000
Double-wall 115-Gallon
260 350 2.6 4.2 140,000
NOTES: Based on 200 °F boiler water temperature and 50 °F potable water inlet temperature.