Installation / Operation Instruction Manual

65
Problem solving
RTG-L-199/160N/X1 – 6 721 827 274 (2022/06)
AA
3)
Condensing unit flue gases temperature [16] above
392 °F (200 °C) and/or flue gases temperature [15]
above 145 °F (63 °C) at the exhaust sensor [15].
Appliance regulates power to protect against
overheating.
Check flue gas temperature sensor.
Check water inlet temperature sensor.
Descale appliance (section 7.3).
1)
AD Flue blockage detected during startup due to
insufficient combustion air. Appliance power derate
and possible reduce of comfort level.
Reset error (press and hold on/off button for 3
seconds).
If the problem persists:
Check air openings and exhaust opening for
obstructions and reset the error.
Check if flue length is according to specification
(section 4.6) and reset the error.
Check if the air filter is dirty or clogged, replace it
if needed.
Perform gas and air tuning ( section 8.11).
1)
BB Fan calibration triggered due to missed ignitions. Check gas inlet pressure ( section 4.14).
1)
Perform gas and air tuning ( section 8.11).
1)
BC Successive fan calibration with similar learned
values.
Check gas inlet pressure ( section 4.14).
1)
Perform gas and air tuning ( section 8.11).
1)
C1
4)
C2
4)
Excessive flue blockage detected during startup due
to insufficient combustion air.
Appliance shuts down for safety.
Reset error (press and hold on/off button for 3
seconds).
If the problem persists:
Check air intake and exhaust pipes and terminals
for obstructions and reset the error.
Check if the air filter is dirty or clogged, clean or
replace it if needed.
Check if flue length is according to specification
(section 4.6) and reset the error.
Perform gas and air tuning ( section 8.11).
1)
C3 Flow sensor [14] does not detect water recirculation. Check pump and connections.
1)
Check recirculation circuit for any blockage.
C5 Bypass water valve [8] disconnected or damaged. Check bypass water valve wire connections.
1)
If the problem persists:
Replace the bypass water valve and/or wire
connections. After valve replacement, proceed
with bypass water valve calibration
(section 6.6).
1)
C7 Fan [2] disconnected or damaged. Check fan wire connections.
Reset error (press and hold on/off button for 3
seconds)
If the problem persists:
Replace the fan and/or wire connections.
1)
Display Description Solution