Installation / Operation Instruction Manual

24
Installation instructions
RTG-L-199/160N/X1 – 6 721 827 274 (2022/06)
Required direct vent terminal clearances (twin pipe / concentric penetration)
Fig. 10
Canadian installations
1)2)
with direct vent terminals
U.S. installations
2)3)
with direct vent
terminals
A Clearance above grade, veranda, porch, deck or balcony 12 in. (30cm) 12 in. (30cm)
B Clearance to window or door that may be opened 36 in. (91cm) 12 in. (30cm) below
or to side of opening;
12 in. (30cm) above
opening.
C Clearance to permanently closed window * *
D Vertical clearance to ventilated soffit located above the terminal within a
horizontal distance of 2 ft (61cm) from the center line of the terminal.
* *
E Clearance to unventilated soffit * *
F Clearance to outside corner * *
G Clearance to inside corner * *
H Clearance to each side of center line extended above meter/regulator
assembly
36 in. (91cm) within a
height 15 ft (4.6m) above
the meter/ regulator
assembly
*