Installation / Operation Instruction Manual

66
Problem solving
RTG-L-199/160N/X1 – 6 721 827 274 (2022/06)
C8 Main water valve [22] disconnected or damaged. Check main water valve wire connections.
1)
If the problem persists:
Replace main water valve and/or wire
connections. After valve replacement, proceed
with main water valve calibration
(section 6.6).
1)
C9 Barometric pressure sensor fault. Reset error (press and hold on/off button for 3
seconds).
If the problem persists:
Replace electronic control unit (ECU).
1)
CA Water flow above 9.2gpm. Disconnect the appliance and purge hydraulic
circuit to remove air.
1)
Install water flow restrictor.
1)
Check water pressure does not exceed 150psi
(section 3.2).
CE
4)
Excessive flue blockage detected during operation
due to excessive pressure on the siphon.
Appliance shuts down for safety.
Reset error (press and hold on/off button for 3
seconds).
If the problem persists:
Check exhaust pipes and terminals for
obstructions and reset the error.
Check if the air filter is dirty or clogged, clean or
replace it if needed.
Check if flue length is according to specification
(section 4.6) and reset the error.
Perform gas and air tuning ( section 8.11).
1)
CF
4)
Excessive flue blockage detected during operation
due to insufficient combustion air.
Appliance shuts down for safety.
Reset error (press and hold on/off button for 3
seconds).
If the problem persists:
Check air intake and exhaust pipes and terminals
for obstructions and reset the error.
Check if the air filter is dirty or clogged, clean or
replace it if needed.
Check if flue length is according to specification
(section 4.6) and reset the error.
Perform gas and air tuning ( section 8.11).
1)
Contact Bradford White support line for
additional information and assistance in case of
installation in dusty areas.
E0 Electronic control unit internal error. Reset error (press and hold on/off button for 3
seconds).
If the problem persists:
Replace electronic control unit.
1)
E1 Hot water temperature above 194 °F (90 °C).
Appliance burner cut off to prevent scalding and
reactivation after cooling down.
Disconnect the appliance and purge hydraulic
circuit to remove air.
If the problem persists:
Reduce setpoint temperature to minimize
temperature instabilities.
Display Description Solution