Installation / Operation Instruction Manual

63
Troubleshooting
RTG-L-199/160N/X1 – 6 721 827 274 (2022/06)
Press the buttons or to adjust parameter value if
power bar level is out of range.
1)
Press the button for 3 seconds and appliance assumes
value.
The value flashes as a sign of confirmation.
Press button to finish the L2 gas adjust (U1).
Parameter D2
Only a qualified technician can change this parameter.
Gas and Air adjustment is complete.
8.11.3 Factory default settings
Restore factory values for P1 Max. Power
To restore factory values for combustion settings.
Proceed with the following steps.
▶Access to menu P1Max. Power.
Press symbols or to select rP (Reset
Parameters).
Press the symbol to select rE.
Press for 3 seconds.
Press the symbol .
The display blinks to confirm change.
Press the symbol .
The factory default values for P1 are restored.
Restore factory values for P2 Low Power
▶Access to menu P2.
Press symbols or to select rP (Reset
Parameters).
Press the symbol to select rE.
Press the symbol for 3 seconds.
Press the symbol .
The display blinks to confirm change.
Press the symbol .
The factory default values for P2 are restored.
1) Increasing L2 value will cause an increase in power bar level
and vice-versa.