Installation / Operation Instruction Manual

48
Troubleshooting
RTG-K-199/160N/X2 – 6 720 813 642 (2022/06)
Press the buttons or to adjust parameter value if
power bar level is out of range.
1)
Fig. 49 Air adjust - A1 parameter
Press the button for 3 seconds and appliance assumes
value.
The value flashes as a sign of confirmation.
Press the button to finish the A1 air adjust.
Press the button or until the display shows "b1".
If b1 is blinking on the display,
Wait until it stops.
Press the button to enter b1.
Open water faucet if display shows water faucet symbol,
see fig. 27, [4].
Display shows the parameter value blinking during
calibration.
Wait until display shows b1 blinking as a sign of calibration
complete.
Press button to finish the b1 automatic air adjust.
Press the button or until the display shows E.
Press the button .
Display shows P1.
Second step - Adjust the minimum power (P2)
Keep hot water faucets opened to adjust minimum power
(P2). The unit will ramp down to low fire and the water flow
should decrease automatically.
Press the buttons or to select P2 (Minimum
Power) menu.
▶Press to enter P2 adjustment.
Display shows E.
▶Press or until L2 appears.
Press the button to enter L2.
Display shows L2 value.
Verify if power bar level is at middle point, see fig. 47.
Press the buttons or to adjust parameter value if
power bar level is out of range.
1)
Press the button for 3 seconds and appliance assumes
value.
The value flashes as a sign of confirmation.
Press button to finish the L2 gas adjust (U1).
Parameter D2
Only a qualified technician can change this parameter.
Gas and Air adjustment is complete.
8.11.3 Factory default settings
Restore factory values for P1 Max. Power
To restore factory values for combustion settings.
Proceed with the following steps.
Access to menu P1 Max. Power.
Press symbols or to select rP reset parameters.
Press the symbol to select rE.
Press for 3 seconds.
▶Press the symbol .
The display blinks to confirm change.
▶Press the symbol .
The factory default values for P1 are restored.
Restore factory values for P2 MIN. Power
Access to menu P2 Min. Power.
Press symbols or to select rP reset parameters.
Press the symbol to select rE.
Press for 3 seconds.
▶Press the symbol .
The display blinks to confirm change.
▶Press the symbol .
The factory default values for P2 are restored.
1) Increasing A1 or L2 value will cause a decrease in power
bar level and vice-versa.