Installation / Operation Instruction Manual

26
Installation instructions
RTG-K-199/160N/X1 – 6 720 817 984 (2022/06)
Required other than direct vent terminal clearances (single pipe penetration)
Fig. 11
Canadian installations
1)2)
with non direct vent
terminals
U.S. installations
2)3)
with
non direct vent terminals
A Clearance above grade, veranda, porch, deck or balcony. 12 in. (30cm) 12 in. (30cm)
B Clearance to window or door that may be opened. 36 in. (91cm) 48 in. (1.2 m) below or to side
of opening; 12 in. (30cm)
above opening)
C Clearance to permanently closed window * *
D Vertical clearance to ventilated soffit located above the
terminal within a horizontal distance of 2 feet (61cm) from the
center line of the terminal
* *
E Clearance to unventilated soffit * *
F Clearance to outside corner * *
G Clearance to inside corner * *
H Clearance to each side of center line extended above meter/
regulator assembly
36 in. (91cm) within a height
15 ft (4.6m) above the
meter/ regulator assembly
*
I Clearance to service regulator vent outlet 36 in. (91cm) *