Installation / Operation Instruction Manual

49
Troubleshooting
RTG-K-199/160N/X2 – 6 720 813 642 (2022/06)
8.12 CO emissions check
In case air/gas combustion adjustment has been performed
check emissions using reference values in tables 23 and 24.
8.12.1 Access to CO
2
measuring port
WARNING:
Only a qualified technician can perform these steps.
This can cause carbon monoxide poisoning.
Follow the instructions carefully.
Allow the appliance to stabilize before performing CO
readings.
Let appliance warm up and wait for 5 minutes for each CO
reading.
This will avoid wrong CO readings.
Open a hot water faucet and let the appliance work for 2 or
5 minutes.
Remove the protection from the front cover, see fig. 50.
Fig. 50 Remove protection
Remove the front cover from the appliance.
Enter in P1 and P2 menus to make the readings.
Place the front cover during the readings.
Insert analyzer probe into the measuring port (approx. 1.5"
inserted), see fig. 51.
Fig. 51 Measuring port