Service Manual

Page 62
Display
Description
Solution
CA
Air in the water circuit (commissioning).
Water flow above maximum value
specified ( 9.24GPM).
Disconnect the appliance and purge hydraulic circuit.1)
Check that water pressure does not exceed 150 psi.
CF
C1
CE
- Vent blockage during operation (Flue
vent outlet or air vent inlet). Insufficient
combustion air.
- Air flow insufficient for start-up (Before
flame ignition).
- Flue outlet vent blockage (exhaust
pressure above siphon water column).
Excessive flue vent pressure.
Remove blockage from the exhaust/intake vent.
Check room air inlet requirements. See Chapter 4.7.
Reset the appliance.
C3
Flow sensor does not detect water
recirculation.
Check pump and connections.
Check recirculation circuit for any blockage.
E0
Internal Failure in ECU
Flow sensor does not detect water recirculation.
E1
Hot water temperature sensor detects
overheating (> 194 °F).
Let the appliance cool down and try again.
Check sensor resistance.
E3
Flue gas temperature sensor detects high
temperature (> 194 °F).
Let the appliance cool down and try again.1)
Check sensor resistance.
E4
Temperature inside the cabinet is above
194 °F.
Check for flue gas leakage inside the cabinet.
Let the appliance cool down and try again.1)
Check sensor resistance.
E5
Copper heat exchanger gas temperature
sensor detects temperature above 392 °F,
the appliance is locked.
Descale appliance.
E7 Internal error
To unlock, reset the appliance by touching the ON/OFF
button for 3 sec.
If the problem persists replace ECU.
E8
Error during ionization test. ECU internal
error.
ECU may need to be replaced.
E9
Thermofuse open. Temperature above 237
°F.
Replace thermofuse cable.
EA
Flame not detected. Ionization loss 9
consecutive times.
Check the gas supply pressure.
To unlock, reset the appliance by touching the ON/OFF
button for 3 sec.
If the problem persists check the ignition electrode or
the ionization electrode.
Check Air/Gas flow adjustment.
EC
Partial ionization loss 5 times.
Check the gas supply pressure.1)
62