Installation / Operation Instruction Manual

29
Installation instructions
RTG-K-199/160N/X1 – 6 720 817 984 (2022/06)
Fig. 15 Horizontal venting installation (combustion air
piping not shown)
[1] Termination
[2] Water heater
[3] Elbow
[4] Horizontal run should slope ¼" per foot upwards to water
heater.
[LA] 12 inches (305 mm) (18 in. for Canada) above maximum
snow level or at least 24 inches (610 mm), whichever is
greater.
NOTICE:
The venting system must be installed in accordance with
the vent system manufacturer’s instructions.
In case vent system manufacturer instructions are not
provided, it is recommended to place pipe supports every
5 feet on horizontal runs, beginning with support near
water heater.
Periodic cleaning of the vent terminal and air-intake
screens is mandatory.
Avoid locating vent terminals near equipment, vegetation,
plants or building features which can be subject to
degradation from exhaust gases.
Fig. 16 Horizontal venting system (sealed combustion)
[1] Intake
[2] Exhaust
Fig. 17 Vent and combustion air pipe position of a sealed
combustion system
[1] Intake
[2] Exhaust
[X] At least 1foot (305mm)