Installation / Operation Instruction Manual

Table Of Contents
Installation instructions
RTG 199 ME – 6 720 811 615 (2014/05)
12
4.3.1 Vent material
Establish vent clearances that comply with the vent manufacturer's
specifications. In all cases, follow local codes. See table 5:
Horizontal venting systems only:
An optional stainless concentric vent/air intake termination can be used
to provide only one penetration point through the exterior wall (see fig.
8, 9 & 10). The concentric vent/air intake kit can be ordered from your
local wholesaler. (Part# ESHCK). Note: Only tee terminals are approved
for use with the concentric vent/air intake kit (see Table 6). Vent piping
and tee terminal used with kit must be from the same vent pipe
manufacturer. The appliance can also be installed with separate air
intake and exhaust piping (see Fig.16).
Fig. 8 Concentric kit part # ESHCK
Fig. 9 Concentric kit vent assembly
Fig. 10 Concentric kit installation
[LA] 12 inches
[LB] 3 inches stainless steel pipe
NOTICE:
In areas where outside temperatures routinely come
close to freezing, sealed combustion operation is
required. Concentric termination or separate
terminations for combustion and vent, must be
installed on the same wall or roof surface; however,
never facing the direction of prevailing winds. Failure
to do so may result in heat exchanger freezing and
bursting. This failure is not covered under the
manufacturer's warranty.
WARNING: Appliance malfunction!
Protect the exhaust and inlet from leaves and debris
by installing a screen on the end of the termination.
¼ " mesh minimum opening recommended on
screen.
Item Diam. Material
Exhaust Vent 3 or 4 inches Sealed single wall stainless steel
(AL29-4C)
Intake Vent PVC Sealed PVC or any other rigid pipe
Table 5 Venting Specifications