7.1 Jumper installation
▶ Install jumpers from the kit on positions JP2 and JP5.
Fig. 7 Jumper configuration
7.2 Software configuration
1. Press ON/OFF button into ON.
2. The key symbol must appear on the display (Fig. 8).
Fig. 8 Key symbol
3. Press and hold buttons or and
simultaneously for 3 seconds, until display reads P2.
4. Use the or button to cycle through different
programs modes, until display shows PE.
5. Press to enter PE adjustment. The current setting will
appear on the display. If not, repeat process.
6. Use the or button on the control board to select
“C”.
7. Hold the button for 5 seconds until display flashes
selection “C”.
8. Press ON/OFF button to turn OFF the appliance.
9. Remove the jumpers from the PCB and store them with the
technical documentation.
▶ Reinstall the rear hatch.
▶ Reinstall the control unit securing the 3 Philips head
screws.
▶ Plug in power cord.
Temperature range
C H
38 °C - 84 °C 38 °C - 60 °C
100 °F - 184 °F 100 °F - 140 °F
Table 4
From now on the temperature range is
100 °F - 184 °F.
For DHW recirculating applications, contact
a qualified technician, to avoid damage in
internal components.
+