Installation Manual

11
Measuring carbon dioxide (CO2)
Outdoor kit – 6 720 811 755 (2014/05)
9 Measuring carbon dioxide (CO
2
)
Note: After installation of the outdoor vent cap, measuring CO
2
for proper levels is recommended before operating the
appliance. See water heater installation manual for details.
To measure CO
2
on this appliance, a test port is available
under the louvered grill on the front of the outdoor vent
cap.
To access test port, remove two screws on either side of
the louvered grill.
Pull louvered grill free from vent cap.
Insert combustion gas analyzer probe approximately 4
inches straight into test port. Do not slope probe up or
down.
Confirm CO
2
is within proper range specified in the water
heater installation manual. Refer to water heater
installation manual if any adjustment is necessary.
When measuring is complete, replace louvered grill with
screws.
Fig. 23
[1] Test port.
WARNING:
Outdoor vent cap will get very hot during
operation.
Ensure the vent cap is cool before
performing the procedure below.