Installation / Operation Instruction Manual

11
Venting (Venting System Condensation) continued-
In order to effectively control condensate from adversely affecting the
mechanical components of the water heater several methods may be
employed:
1. For horizontal installations the vent pipe can be installed with a downward
slope (not less than 1/8 in (3 cm)) and away from the blower.
2. In order to prevent condensate from draining back into the blower (vertical or
horizontal runs), an optional condensate kit is available as a service part
(Condensate kit, p/n 239-45875-00). A factory supplied exhaust adapter with
drain outlet mounts directly to the blower outlet and is secured with two hose
clamps, one to the blower and the other to the vent pipe. Tubing is provided
to drain any accumulated condensate away from the water heater and to a
suitable drain. The kit comes complete with instructions for proper
installation.
Venting Specifications for 48 Gallon (181.6 L):
This water heater is a power vented appliance and is designed to vent its
products of combustion through 3 in (7.6 cm) or 4 in (10.2 cm) diameter vent
pipe to the outdoors. This water heater may be either vented horizontally
through the wall or vertically through the roof. Use a 3 in (7.6 cm) to 4 in
(10.2 cm) reducer to connect to the vent outlet when using 4 in (10.2 cm) vent
pipe. Apply the proper cement at the joint locations. Table 1 lists the maximum
vent lengths for this water heater using 3 in (7.6 cm) vent pipe. If possible,
locate the water heater so that the venting length and number of elbows are
kept to the minimum distance necessary to reach the outside. If the installation
requires venting lengths that exceed the lengths listed for 3 in (7.6 cm) vent
pipe in Table 1, then use 4 in (10.2 cm) vent pipe for the vent connector.
Table 2 lists the venting distances allowed with 4 in (10.2 cm) diameter vent
pipe. When venting with 4 in (10.2 cm) vent pipe, use a 4 in (10.2 cm) to
3 in (7.6 cm) reducer to exit through the building wall with 3 in (7.6 cm) vent
pipe. Use the 3 in (7.6 cm) vent terminal supplied with the water heater to
terminate on the outside of the building. If replacing a water heater and the
existing vent terminal supplied with the new water heater, replacement of the
vent terminal is not required. The vent terminal should be inspected to make
sure that it is in good condition.
If the length of 3 in (7.6 cm) vent pipe needed to go through the wall is greater
than 14 in (35.5 cm), use 4 in (10.2 cm) to go through the wall and reduce to 3
in (7.6 cm) vent pipe immediately after exiting the outside wall. Refer to the
venting illustrations on the following pages. Make sure the vent pipe terminal
elbow fitting is at least 1 in (2.5 cm) away from the edge of the wall.