Installation / Operation Instruction Manual
13
Venting continued-
Table 2 lists the venting distances allowed with 3” (7.6 cm) diameter vent pipe.
When venting with 3” (7.6 cm) vent pipe, use a 3” (7.6 cm) to 2” (5.1 cm)
reducer to exit through the building wall with 2” (5.1 cm) vent pipe. Use the 2”
(5.1 cm) vent terminal supplied with the water heater to terminate on the
outside of the building. If the length of the 2” (5.1 cm) needed to go through the
wall is greater than 14” (35.6 cm), use 3” (7.6 cm) vent pipe to go through the
wall and reduce to 2” (5.1 cm) vent pipe immediately after exiting the outside
wall. Refer to the venting illustrations on the following pages. Make sure the
vent pipe terminal is at least 1” (2.5 cm) away from the edge of the wall.
TABLE 1
VENT CONNECTOR LENGTHS FOR 2” (5.1cm) DIAMETER VENT PIPE
Terminating
# of 90 Elbows
(excluding vent
terminal)
Max straight
Length
ft (m)
Min straight
Length
ft (m)
Through the Wall 1 45 (13.7) 2 (.6)
Through the Wall 2 40 (12.2) 2 (.6)
Through the Wall 3 35 (10.7) 2 (.6)
Through the Wall 4 30 (9.1) 2 (.6)
Through the Roof 0 50 (15.2) 7 (2.1)
Through the Roof 1 45 (13.7) 7 (2.1)
Through the Roof 2 40 (12.2) 7 (2.1)
Through the Roof 3 35 (10.7) 7 (2.1)
Through the Roof 4 30 (9.2) 7 (2.1)