Installation / Operation Instruction Manual
16
Venting continued-
TABLE 3
3 inch (7.6 cm) Vent Connector Lengths From Inside Wall For Low Ground
Clearance Installations
Terminating
# of Elbows
(excl. vent
term.)
Max Straight
Length ft (m)
Min
Straight
Length
ft (m)
55 and 75 gal.
(2) 90 Elbows with (1) 90
Elbow
1
35 (10.7)
5 (1.5)
(2) 90 Elbows with (1) 90
Elbow
2
30 (9.2)
5 (1.5)
(2) 90 Elbows with (1) 90
Elbow
3
25 (7.6)
5 (1.5)
(2) 90 Elbows with (1) 90
Elbow
4
20 (6.1)
5 (1.5)
TABLE 4
4 inch (10.2 cm) Vent Connector Lengths From Inside Wall For Low Ground
Clearance Installations
Terminating (Reduce 4 inch to
3 inch)
(Reduce 10.1 cm to 7.6 cm)
# of Elbows
(excl. vent
term.)
Max Straight
Length ft (m)
Min
Straight
Length
ft (m)
55 and 75 gal.
(2) 90 Elbows with (1) 90
Elbow
1
165 (50.3)
10 (3.1)
(2) 90 Elbows with (1) 90
Elbow
2
160 (48.8)
10 (3.1)
(2) 90 Elbows with (1) 90
Elbow
3
155 (47.2)
10 (3.1)
(2) 90 Elbows with (1) 90
Elbow
4
150 (45.7)
10 (3.1)
(2) 90 Elbows with (1) 90
Elbow
5
145 (44.2)
10 (3.1)
HIGH ALTITUDE INSTALLATIONS FOR ELEVATIONS OVER 2,500 FEET
(762 m) ABOVE SEA LEVEL
The capacity of the induced draft blower declines with increasing altitude due to
a reduction in the air density. In order to assure safe and reliable performance
of the water heater, contact the supplier for high altitude kit.