Venting System Condensation
Condensate formation does not occur in all installations of power vented water heaters
but should be protected against on installations where condensation can form in the
venting system.
Formation of condensation in the venting system of Power Vented water heaters is
dependent upon installation conditions including, but not limited to:
ambient temperature and humidity of installation location,
ambient temperature and humidity of venting space,
vent distance and slope,
and product usage.
In order to effectively control condensate from adversely affecting the mechanical
components of the water heater several methods may be employed:
1. For horizontal installations the vent pipe can be installed with a downward
slope (not less than 1/8 in. (3 cm)) and away from the blower.
2. In order to prevent condensate from draining back into the blower (vertical or
horizontal runs), an optional condensate kit is available as a service part
(Condensate kit, p/n 239-45875-00). A factory supplied exhaust adapter with
drain outlet mounts directly to the blower outlet and is secured with two hose
clamps, one to the blower and the other to the vent pipe. Tubing is provided to
drain any accumulated condensate away from the water heater and to a
suitable drain. The kit comes complete with instructions for proper installation.
If replacing a water heater and the existing vent terminal is identical to the vent terminal
supplied with the new water heater, replacement of the vent terminal is not required. The
vent terminal should be inspected to make sure that it is in good condition.
Venting Specifications for 55 gal (208.2 L), 75 gal (283.9 L)
This water heater is a power vented appliance and is designed to vent its products of
combustion through 3 in. (7.6 cm) or 4 in. (10.2 cm) diameter vent pipe to the outdoors.
This water heater may be either vented horizontally through the wall or vertically through
the roof. Use a 3 in. (7.6 cm) to 4 in. (10.2 cm) reducer to connect to the vent outlet
when using 4 in. (10.2 cm) vent pipe. Apply the proper cement at the joint locations.
Table 1 lists the maximum vent lengths for this water heater using 3 in. (7.6 cm) vent
pipe. If possible, locate the water heater so that the venting length and number of
elbows are kept to the minimum distance necessary to reach the outside. If the
installation requires venting lengths that exceed the lengths listed for 3 in. (7.6 cm) vent
pipe in Table 1, then use 4 in. (10.2 cm) vent pipe for the vent connector.
Table 2 lists the venting distances allowed with 4 in. (10.2 cm) diameter vent pipe. When
venting with 4 in. (10.2 cm) vent pipe, use a 4 in. (10.2 cm) to 3 in. (7.6 cm) reducer to
exit through the building wall with 3 in. (7.6 cm) vent pipe. If replacing a water heater and
the existing vent terminal is identical to the vent terminal supplied with the new water
heater, replacement of the vent terminal is not required. The vent terminal should be
inspected to make sure that it is in good condition. Use the 3 in. (7.6 cm) vent terminal
supplied with the water heater to terminate on the outside of the building. If the length of
3 in. (7.6 cm) vent pipe needed to go through the wall is greater than 14 in. (35.5 cm),
use 4 in. (10.2 cm) to go through the wall and reduce to 3 in. (7.6 cm) vent pipe
immediately after exiting the outside wall. Refer to the venting illustrations on the
following pages. Make sure the vent pipe terminal elbow fitting is at least 1 in. (2.5 cm)
away from the edge of the wall.