Venting continued-
WARNING
This water heater must be properly vented and connected to an approved vent
system in good condition. DO NOT operate water heater with the absence of an
approved vent system. A clean and unobstructed vent system is necessary to allow
noxious fumes that could cause injury or loss of life to vent safely and will contribute
toward maintaining the water heaters efficiency. The acceptance of the venting
system is dependent upon full compliance with these installation instructions. When
an existing Category I appliance is removed or replaced, the original venting system
may no longer be sized to properly vent the attached appliances.
For installations in Canada, the venting system must NOT pass through rated fire
separations.
The venting system must be free to expand and contract. This venting system must
be supported in accordance with these instructions.
NOTICE
For installations in Canada, field supplied vent piping must comply with CAN/CGA
B149.1 (latest edition) and be certified to the Standard For Type BH, Class II, 65°C,
Gas Venting Systems, ULC S636. Components of this listed system shall not be
interchanged with other vent systems or unlisted pipe/fittings. All components and
specified primers and cements of the certified vent system must be from a single
system manufacturer and not intermixed with other system manufacturer’s vent
system parts. The supplied vent connector and vent termination are certified under
ULC S636 and are also certified as part of the water heater. Refer to the following
tables for approved venting materials, primers, and cements. All approved primers
and cements are to be used within their marked time limitations.
Approved Venting Materials
For installations in the US only
DWV Sch. 40 PVC (ASTM D-2665)
PVC Sch. 40 (ASTM-D1785)
CPVC Sch. 40 (ASTM-F441, ASTM D-
2846)
PVC and CPVC (UL 1738, ULC S636)
ABS Sch. 40 DWV (ASTM D2661)
Polypropylene (UL 1738, ULC S636)
For installations in CANADA
ULC S636 approved PVC for flue gas
venting rated Class II, 65°C
ULC S636 approved CPVC for flue
gas venting rated Class II, 65°C
ULC S636 approved Polypropylene
for flue gas venting rated Class II,
65°C
Approved Primers and Cements
For installations in the US only
PVC and CPVC Primer (ASTM-F656)
PVC Cement (ASTM D-2564)
CPVC Cement (ASTM F493)
ABS Primer and Cement (ASTM D-
2235)
For installations in CANADA
ULC S636 approved Primer and
Cement for flue gas venting rated
Class II, 65°C
NOTICE
Use of cellular core PVC (ASTM F891), cellular core CPVC, or Radel
®
(polyphenosulfone) in non-metallic venting systems is prohibited and covering non-
metallic venting with thermal insulation is prohibited.