Installation / Operation Instruction Manual
10
WARNING
Risk of carbon monoxide poisoning or fire due to joint separation or
pipe breakage.
This water heater must be properly vented and connected to an approved
vent system in good condition. DO NOT operate water heater with the
absence of an approved vent system. A clean and unobstructed vent
system is necessary to allow noxious fumes that could cause injury or
loss of life to vent safely and will contribute toward maintaining the water
heater’s efficiency. The acceptance of the venting system is dependent
upon full compliance with these installation instructions. When an existing
Category I appliance is removed or replaced, the original venting system
may no longer be sized to properly vent the attached appliances.
For installations in Canada, the venting system must NOT pass through
rated fire separations.
The venting system must be free to expand and contract. This venting
system must be supported in accordance with these instructions.
Approved Venting Materials
For installations in the US only
• PVC DWV Sch. 40 (ASTM D-2665)
• PVC Sch. 40 (ASTM-D1785)
• CPVC Sch. 40 (ASTM-F441, ASTM
D2846)
• PVC and CPVC (UL 1738, ULC
S636)
• ABS Sch. 40 DWV (ASTM D2661)
• Polypropylene (UL 1738, ULC S636)
For installations in CANADA
• ULC S636 approved PVC for flue
gas venting rated Class II, 65°C
• ULC S636 approved CPVC for
flue gas venting rated Class II,
65°C
• ULC S636 approved
Polypropylene for flue gas venting
rated Class II, 65°C
Approved Primers and Cements
For installations in the US only
• PVC and CPVC Primer (ASTM-F656)
• PVC Cement (ASTM D-2564)
• CPVC Cement (ASTM F493)
• ABS Primer and Cement (ASTM D-
2235)
For installations in CANADA
• ULC S636 approved Primer and
Cement for flue gas venting rated
Class II, 65°C
NOTICE
Use of cellular core PVC (ASTM F891), cellular core CPVC, or Radel
®
(polyphenosulfone) in non-metallic venting systems is prohibited and
covering non-metallic venting with thermal insulation is prohibited.