Installation / Operation Instruction Manual

10
Venting continued-
Vent pipes serving power vented appliances are classified by building codes as “vent
connectors”. Required clearances from combustible materials must be provided in
accordance with information in this manual under LOCATION OF WATER HEATER and
CLEARANCES, and with National Fuel Gas Code and local codes.
Clearance to combustibles for all venting pipes
and terminals
For installations in the US
0” minimum
For installations in Canada
Refer to vent pipe and terminal
manufacturer’s installation instructions
for clearances to combustibles
DO NOT place insulation or other materials in the required clearance spaces
between the venting to combustible material unless otherwise specified.
WARNING
Risk of carbon monoxide poisoning or fire due to joint separation
or pipe breakage.
This water heater must be properly vented and connected to an
approved vent system in good condition. DO NOT operate water heater
with the absence of an approved vent system. A clean and
unobstructed vent system is necessary to allow noxious fumes that
could cause injury or loss of life to vent safely and will contribute toward
maintaining the water heater’s efficiency. The acceptance of the venting
system is dependent upon full compliance with these installation
instructions.
Venting system must not pass through rated fire separations.
The venting system must be free to expand and contract. This venting
system must be supported in accordance with these instructions.