SERVICE PROCEDURE RG-VI
Gas Control Testing, Disassembly &
Replacement (Honeywell)
MANIFOLD PRESSURE TESTING (this procedure presumes a maximum line pressure of 14.0" w.c.)
Step 1. Set the gas control to the OFF position.
Step 2. Remove pressure tap plug and install
1/8" NPT pipe, coupling, & pressure tap.
Step 3. Connect manometer to pressure tap.
Step 4. Follow instructions located on the lighting
instructions label and proceed to light the main
burner and observe manometer reading.
Step 5. Proper operating range for natural gas is: 4.0" ±0.5" w.c.
Proper operating range for LP gas is: 10.0" ±0.5" w.c.
Step 6. If pressure is within the range specified in the
previous step, set gas control knob to the OFF
position, remove manometer and pressure tap, and
replace pressure tap plug. Check for gas leaks prior
to placing water heater back into operation by
following the instructions located on the lighting
instruction label or the lighting instructions located in the
installation and operation manual.
Step 7. If gas pressure is outside the specification noted above,
refer to Honeywell gas control Testing, Disassembly,
and Replacement to replace gas control or valve body.
THERMOPILE TESTING
See SERVICE PROCEDURE RG-II
The Honeywell Gas Control is designed with an ECO device that will reset.
To reset the Gas Control after an error code (4), turn the Gas Control knob to the OFF position and wait a
minimum of (5) minutes before relighting following the instructions located on the lighting instruction label or
the lighting instructions located in the installation and operation manual.
ECO (Energy Cut Off) TESTING
Gas Control shown in the OFF position
Pressure Tap
Shown Installed