Quick Service Guide
Technical Support
800-334-3393
www.bradfordwhite.com
Atmospheric Vent - White Rodgers Electronic
NOTE: Check all wire connections
Check gas inlet and manifold gas pressure
Check for grounding connections
Error Code Definition Service Action Possible Parts Needed
No LED No pilot light / heater not in operation Follow lighting instructions on the water heater 1) None
One flash & four second pause Knob in pilot position or thermostat satisfied None 1) None
One flash every second Thermostat calling for heat None 1) None
Two flashes & three second pause Weak pilot signal detected
Verify pilot is lit
Check thermopile voltage output
Check wire connections at gas valve
1) Pilot assembly
2) Gas valve
Four flashes & three second pause High tank temperature
Check if tank temperature exceeds setpoint
Check operation of control
Verify no heat migration in plumbing system
1) Gas valve
Five flashes & three second pause Gas valve fault
Turn to off, wait for LED to go out, relight –
Turn knob to setpoint
If burner fires code will clear after 5 minutes
If problem persists, replace gas valve
1) Gas valve
Solid ON
Not an error-indicates that the control is shutting down
Control knob turned to the off position
None; wait until LED goes out before attempting to
relight
1) None
CQSG-AV-WR-0520