User Guide

Condensing PDV Series
7
Vent Tables
2" Diameter (5.1 cm) Vent Connector Lengths
Terminating
Elbows
Maximum Straight
Length ft. (m)
Minimum Straight
Length ft. (m)
Through the Wall
45 (13.7)
2 (.6)
Through the Wall
40 (12.2)
2 (.6)
Through the Wall
35 (10.7)
2 (.6)
Through the Wall
30 (9.2)
2 (.6)
Through the Roof
50 (15.2)
7 (2.1)
Through the Roof
45 (13.7)
7 (2.1)
Through the Roof
40 (12.2)
7 (2.1)
Through the Roof
35 (10.7)
7 (2.1)
Through the Roof
4
30 (9.2)
7 (2.1)
3" Diameter (10.2 cm) Vent Connector Lengths
Terminating
Elbows
Maximum Straight
Length ft. (m)
Minimum Straight
Length ft. (m)
Through the Wall
115 (35.0)
10 (3.1)
Through the Wall
110 (33.5)
10 (3.1)
Through the Wall
105 (32.0)
10 (3.1)
Through the Wall
100 (30.5)
10 (3.1)
Through the Wall
95 (29.0)
10 (3.1)
Through the Roof
120 (36.6)
15 (4.6)
Through the Roof
115 (35.0)
15 (4.6)
Through the Roof
110 (33.5)
15 (4.6)
Through the Roof
105 (32.0)
15 (4.6)
Through the Roof
100 (30.5)
15 (4.6)
4" Diameter (10.2 cm) Vent Connector Lengths
Terminating
Maximum Straight
Length ft. (m)
Minimum Straight
Length ft. (m)
Through the Wall
180 (54.9)
10 (3.1)
Through the Wall
175 (53.3)
10 (3.1)
Through the Wall
170 (51.8)
10 (3.1)
Through the Wall
165 (50.3)
10 (3.1)
Through the Wall
5
160 (48.8)
10 (3.1)
Through the Roof
180 (54.9)
15 (4.6)
Through the Roof
175 (53.3)
15 (4.6)
Through the Roof
170 (51.8)
15 (4.6)
Through the Roof
165 (50.3)
15 (4.6)
Through the Roof
160 (48.8)
15 (4.6)
7