Install Instructions
34
Water Connections continued-
WARNING
For protection against excessive temperatures and pressure, install
temperature and pressure protective equipment required by local codes,
but not less than a combination temperature and pressure relief valve
certified by a nationally recognized testing laboratory that maintains
periodic inspection of production of listed equipment or materials as
meeting the requirements of the Standard for Relief Valves and Automatic
Gas Shutoff Devices for Hot Water Supply Systems, ANS Z21.22 or the
Standard CAN1-4.4. Temperature and Pressure and the Standard CAN1-
4.4, Temperature, Pressure, Temperature and Pressure Relief Valves and
Vacuum Relief Valves. The combination temperature and pressure relief
valve must be marked with a maximum set pressure not to exceed the
maximum working pressure of the water heater. The combination
temperature and pressure relief valve must also have an hourly rated
temperature steam BTU discharge capacity not less than the hourly rating
of the water heater.
Install the combination temperature and pressure relief valve into the
opening provided and marked for this purpose on the water heater.
Note: Some models may already be equipped or supplied with a
combination temperature and pressure relief valve. Verify that the
combination temperature and pressure relief valve is in compliance with
local codes. If the combination temperature and pressure relief valve does
not comply with local codes, replace it with one that does. Follow the
installation instructions above on this page.
Install a discharge line so that water discharged from the combination
temperature and pressure relief valve will exit within 6 in. (15.2 cm) above
or any distance below the structural floor and cannot contact any live
electrical part. The discharge line is to be installed to allow for complete
drainage of both the combination temperature and pressure relief valve
and the discharge line. The discharge opening must not be subjected to
blockage or freezing. DO NOT thread, plug or cap the discharge line. It is
recommended that a minimum clearance of 4 in. (10.2 cm) be provided on
the side of the water heater for servicing and maintenance of the
combination temperature and pressure relief valve.
DO NOT place a valve between the combination temperature and
pressure relief valve and the tank.