Install Instructions

18
Venting continued-
Power Direct Vent
Through The Wall Venting (Horizontal Venting With Standard Vent
Terminals):
Cut two 2 1/2 in. (6.4 cm) diameter holes in the wall at the point where the vent
connector is going to pass through the wall. Use the proper cement to secure
the 45° vent terminal provided with the water heater to the vent connector. The
distance between the edges of the 45° vent terminal and the exterior wall must
be 1 in. (2.5 cm) (see Figure 3). The exhaust and intake must not be less than
16 in. (40.6 cm) apart, and the exhaust terminal must be a minimum of 2 in.
(5.1 cm) higher than the intake terminal (see Figure 4a). Use the proper cement
and assembly procedures to secure the vent connector joints between the
terminal and the blower outlet. Provide support brackets for every 5 ft. (1.5 m)
of horizontal vent.
2” VENT INSTALLATION
3” VENT INSTALLATION
Figure 3 Vent Installations