Venting continued-
TABLE 1 – VENT CONNECTOR LENGTHS
FOR 2” (5.1 cm) DIAMETER VENT PIPE
Terminating
# of 90° Elbows
(excl. vent term)
Maximum straight
Length ft (m)
Min. straight
Length ft (m)
Through the Wall
1
45 (13.7)
2 (.6)
Through the Wall
2
40 (12.2)
2 (.6)
Through the Wall
3
35 (10.7)
2 (.6)
Through the Wall
4
30 (9.1)
2 (.6)
Through the Roof
0
50 (15.2)
7 (2.1)
Through the Roof
1
45 (13.7)
7 (2.1)
Through the Roof
2
40 (12.2)
7 (2.1)
Through the Roof
3
35 (10.7)
7 (2.1)
Through the Roof
4
30 (9.1)
7 (2.1)
TABLE 2 -VENT CONNECTOR LENGTHS
FOR 3” (7.6 cm) DIAMETER VENT PIPE
Terminating
# of 90° Elbows
(excl. vent term)
Maximum straight
Length ft (m)
Min. straight
Length ft (m)
Through the Wall
1
115 (35.0)
10 (3.1)
Through the Wall
2
110 (33.5)
10 (3.1)
Through the Wall
3
105 (32.0)
10 (3.1)
Through the Wall
4
100 (30.5)
10 (3.1)
Through the Wall
5
95 (29.0)
10 (3.1)
Through the Roof
0
120 (36.6)
15 (4.6)
Through the Roof
1
115 (35.0)
15 (4.6)
Through the Roof
2
110 (33.5)
15 (4.6)
Through the Roof
3
105 (32.0)
15 (4.6)
Through the Roof
4
100 (30.5)
15 (4.6)
TABLE 3 -VENT CONNECTOR LENGTHS
FOR 4” (10.2 cm) DIAMETER VENT PIPE
Terminating
# of 90° Elbows
(excl. vent term)
Maximum straight
Length ft (m)
Min. straight
Length ft (m)
Through the Wall
1
175 (53.3)
10 (3.1)
Through the Wall
2
170 (51.8)
10 (3.1)
Through the Wall
3
165 (50.3)
10 (3.1)
Through the Wall
4
160 (48.8)
10 (3.1)
Through the Wall
5
155 (47.2)
10 (3.1)
Through the Roof
0
180 (54.9)
15 (4.6)
Through the Roof
1
175 (53.3)
15 (4.6)
Through the Roof
2
170 (51.8)
15 (4.6)
Through the Roof
3
165 (50.3)
15 (4.6)
Through the Roof
4
160 (48.8)
15 (4.6)
NOTE: When using 3” (7.6 cm) or 4” (10.2 cm) vent pipe, use a reducer to 2” (5.1 cm)
and exit the building wall with 2” (5.1 cm) vent pipe using the 2” (5.1 cm) 45 vent
terminal supplied. Two 45 elbows are equivalent to one 90 elbow. Each 90° elbow is
equivalent to 5 feet (1.5 m) of straight vent pipe.