Manual

5
SECTION II: SPECIFICATIONS
Flow Rate vs Temperature Rise Curve for EVERHOT IGE model series
0
1
2
3
4
5
6
7
8
9
0 25 50 75 100 125 150
T – Temperature Rise (°F)
Max. Flow (gpm)*
*Note: The maximum flow is based upon a minimum water pressure of 30 PSI
Max. Flow Rate @ Degree Temperature Rise
Model No.
Max.
Input
Rating
Btu/hr.
Min.
Input
Rating
Btu/hr.
Temp Rise
40F
60F
80F
100F
120F
140F
IGE-199R-10N
IGE-199R-10X
IGE-199C-5N
IGE-199C-5X
199,000
15,000 Flow Rate
Gal/Min.
7.3 5.9 4.2 3.3 2.8 2.4
First Hour
Supply
Gal/Hr.
438 354 252 198 168 144
Max. Flow Rate @ Degree Temperature Rise
Model No.
Max.
Input
Rating
kW/hr.
Min.
Input
Rating
kW/hr.
Temp Rise
22C
33C
44C
56C
67C
78C
IGE-199R-10N
IGE-199R-10X
IGE-199C-5N
IGE-199C-5X
58.3
4.4 Flow Rate
Liters/
Min.
27.6 22.3 15.9 12.5 10.6 9.1
First Hour
Supply
Liters/Hr.
1656 1338 954 750 636 545