Installation / Operation Instruction Manual
7
Water Connections continued-
WARNING
For protection against excessive temperatures and pressure, inst all
temperature and pressure protective equipment required by local
codes, but not less than a combination temperature and pressure relief
valve certified by a nationally recognized testing laboratory that
maintains periodic inspection of production of listed equipment or
materials, as meeting the Requirements for Relief Valves and
Automatic Gas Shutoff Devices for Hot Water Supply Systems, ANSI
Z21.22, and the Standard CAN1-4.4 Temperature, Pressure,
Temperature and Pressure Relief Valves and Vacuum Relief Valves.
The combination temperature and pressure relief valve must be
marked w ith a maximum set pressure, not to exceed the maximum
working pressure of the w ater heater. The combination temperature
and pressure relief valve shall also have an hourly rated temperature
steam BTU discharge capacity not less than the hourly input rating of
the water heater.
Install the combination temperature and pressure relief valve into the
opening provided and marked for this purpose on the water heater
Note: Some models may already be equipped or supplied w ith a
combination temperature and pressure relief valve. Verify that the
combination temperature and pressure relief valve complies with local
codes. If the combination temperature and pressure relief valve does
not comply with local codes, replace it w ith one that does. Follow the
installation instructions above on this page.
Install a discharge line so that water discharged from the combination
temperature and pressure relief valve w ill exit within six (6) inches
(15.3 cm) above, or any distance below the structural floor and
cannot contact any live electrical part. The discharge line is to be
installed to allow for complete drainage of both the temperature and
pressure relief valve and the discharge line. The discharge opening
must not be subjected to blockage or freezing. DO NOT thread, plug
or cap the discharge line. It is recommended that a minimum of four
(4) inches (10.2 cm) be provided on the side of the water heater for
servicing and maintenance of the combination temperature and
pressure relief valve.
Do not place a valve betw een the combination temperature and
pressure relief valve and the tank.