Pre-installation continued-
IMPORTANT DECISIONS REQUIRED BEFORE
INSTALLATION
SIZING
1. Boiler DOE Heating Capacity – The indirect-fired water heater
will provide the rated performance only if used in conjunction
with a heat source with a DOE heating capacity (Heat Output) at
least as much as the minimum noted in Table 3. If the heat
source has less capacity, the output of the tank will be reduced.
To determine the approximate reduction in output from the tank
use the following formula:
New Rating = (maximum continuous draw rating) x
Actual Output of Heat Source
Minimum Output of Heat Source
For example, what would the continuous draw rating be if a 50-gallon
indirect-fired water heater were installed with a heat source having a
DOE heating capacity of 50,000 BTU/h?
Answer:
New Rating
= 85 gal/hr x (50,000 BTU/h)/(58,000 BTU/h)
= 85 gal/hr x 0.862 = 73 gal/hr
NOTICE
Increasing the boiler DOE heating capacity above the values listed in
Table 3 will not increase the rating of the water heater.
2. Circulator Sizing – Refer to Table 5 for the corresponding
pressure drop through the coil for the given model. Calculate the
pressure drop of all straight pipe and fittings on the supply and
return of the water heater at the selected flow rate. Add the
piping/fitting pressure drop to the pressure drop through the water
heater coil.
Select a circulator that will provide an appropriate flow rate at the
combined pressure drop.