Installation / Operation Instruction Manual
23
Electrical Connections continued-
GENERAL INSTALLATIONS
If a circulator is used to control the heating fluid flow from the
water heater to the boiler, a zone relay is required between the
water heater thermostat and the boiler. Connect the white wire on
the water heater to one leg of the circulator. The second leg of the
circulator is to be connected to “L2” (120V neutral). Connect the
white wire on the water heater to one leg of the zone relay. The
second leg of the zone relay is to be connected to “L2” (120V
neutral). The contact side of the zone relay is to be connected to
the boiler operating control (see figure 5). Connect the black wire
on the water heater to “L1” (120V hot). These connections enable
water heater thermostat to control the circulator, the zone relay,
and the boiler operating control.
Figure 5 – Electrical Connection with Circulator
If a zone valve to used to control the heating fluid flow from the boiler
to the water heater, a zone step-down transformer is required
between the water heater thermostat and the zone valve. Connect
the white wire on the water heater to one leg of the transformer
primary side. The second leg of the primary side is to be connected
to “L2” (120V neutral). The secondary side of the transformer is to be
connected to the zone valve coil. The contact side of the zone valve
is to be connected to the boiler operating control. Connect the black
wire on the water heater to “L1” (120V hot) (see figure 6). These
connections enable the water heater thermostat to control the zone
valve and the boiler operating control.