Installation / Operation Instruction Manual

14
Pre-installation continued-
SYSTEM ZONE CONTROL
The indirect-fired water heater must be installed as a zone
separate from the space heating system. The domestic hot water
zone’s piping and circulator must be sized for a minimum flow
rate with all zones in use and a maximum flow rate with only the
water heater in use. For this reason, the preferred method of
zone control is with circulators.
1. Circulators With space heating zones using circulators,
the indirect-fired heater should be added as an additional
zone with a circulator.
2. Zone Valves Select a valve with a low-pressure drop to
assure adequate flow through the water heater.
3. Hybrid The space heating zone can be zoned using zone
valves and the indirect-fired heater zoned with a circulator.
DOMESTIC HOT WATER PRIORITY
Two options are available, Priority and Non-Priority.
1. Priority Demand for space heating is interrupted or
postponed until the domestic hot water demand is satisfied.
This option provides maximum delivery of domestic hot
water. Priority is recommended when:
a) Boiler net output is 100,000 Btu per hour or less, or
b) When boiler output required to satisfy domestic hot
water demand is at least 50% of the boiler output
required to satisfy space heating demand, or
c) When an interruption in space heating can be tolerated
during a long domestic hot water draw.
2. Non-Priority Boiler output is divided between space
heating and domestic hot water heating. Delivery of
domestic hot water can be reduced during simultaneous
space and domestic hot water heating operations,
depending on such factors as boiler output, boiler over-
sizing, number of space heating zones calling for heat, and
the ratio of domestic hot water load to space heating load.