Pre-installation continued-
IMPORTANT DECISIONS REQUIRED BEFORE
INSTALLATION
SIZING
1. Boiler DOE Heating Capacity The indirect-fired water
heater will provide the rated performance only if used in
conjunction with a heat source with a DOE heating
capacity (Heat Output) at least as much as the minimum
noted in Table 3. If the heat source has less capacity, the
output of the tank will be reduced. To determine the
approximate reduction in output from the tank use the
following formula:
New Rating = (maximum continuous draw rating) x
Actual Output of Heat Source
Minimum Output of Heat Source
For example, what would the continuous draw rating be if a
50-gallon indirect-fired water heater were installed with a heat
source having a DOE heating capacity of 50,000 BTU/h?
Answer:
New Rating
= 85 gal/hr x (50,000 BTU/h)/(58,000 BTU/h)
= 85 gal/hr x 0.862 = 73 gal/hr
NOTICE
Increasing the boiler DOE heating capacity above the values
listed in Table 3 will not increase the rating of the water heater.
2. Circulator Sizing Refer to Table 5 for the corresponding
pressure drop through the coil for the given model. Calculate
the pressure drop of all straight pipe and fittings on the supply
and return of the water heater at the selected flow rate. Add
the piping/fitting pressure drop to the pressure drop through
the water heater coil.
Select a circulator that will provide an appropriate flow rate at
the combined pressure drop.