Installation / Operation Instruction Manual
12
General Information continued-
WARNING
Install a discharge line so that water discharged from the
temperature and pressure relief valve will exit within six (6) inches
above, or any distance below, the structural floor and cannot
contact any live electrical part. The discharge line is to be installed
to allow for complete drainage of both the temperature and
pressure relief valve and the discharge line. The discharge opening
must not be subjected to blockage or freezing. DO NOT thread,
plug, or cap the discharge line. It is recommended that a minimum
clearance of four (4) inches be provided on the side of the water
heater for servicing and maintenance of the combination
temperature and pressure relief valve.
DO NOT place a valve between the combination temperature and
pressure relief valve and the tank!
SACRIFICIAL ANODES – Two sacrificial anode rods have been
installed in the tank head to extend tank life. The removal of any
anodes, except for inspection and/or replacement, will nullify the
warranty. The anode rods should be inspected annually to
determine the amount of sacrificial decay and replaced when
necessary to prolong tank life. Water conditions in your area will
influence the time interval for inspection and replacement of the
anode rod. The use of a water softener may increase the speed of
anode consumption. More frequent inspection of the anode is
needed when using softened (or phosphate treated) water.
Contact the plumbing professional who installed the water heater
or the manufacturer, listed on the rating plate, for anode
replacement information.
SECTION IV
PRE-INSTALLATION
UNPACKING
INSPECT SHIPMENT carefully for any signs of damage. If damage
is noted, do not install the product. Contact the shipper or
manufacturer. All equipment is carefully manufactured, inspected,
and packed. Our responsibility ceases upon delivery of the
packaged water heater to the carrier in good condition.
NOTE: Any claims for damage or shortage in shipment must be
filed immediately against the carrier by the consignee.
This water heater MUST be installed indoors out of the wind and
weather.