Installation / Operation Instruction Manual
30
Gas Connections
The gas supply lines must meet all requirements of the National Fuel Gas Code
(ANSI Z223.1-Latest Edition), or in Canada CAN/CGA B149.1 Natural Gas
Installation Code (Latest Edition) or CAN/CGA B149.2 Propane Installation
Code (Latest Edition).
The minimum permissible gas supply pressure for the purpose of input
adjustment is one (1.0) inch (0.25 kPa) water column above the operating
manifold pressure. See the rating plate and gas valve for the manifold pressure
and gas type. The maximum permissible gas supply pressure is fourteen (14.0)
inches (3.5 kPa) water column for natural gas and liquefied petroleum
gases/propane gas.
1. Connect this water heater only to the type of gas (Natural or Propane gas)
as shown on the rating plate. Use clean black iron pipe or equivalent
material approved by local codes and ordinances. (Dirt and scale from the
pipe can enter the gas valve and cause it to malfunction). The inlet gas line
must have a minimum length of three (3) inches (7.6 cm) drip leg (sediment
trap) installed as close to the water heater’s gas valve as possible. A
ground joint union must be installed as close to the water heater as
possible in the gas supply line feeding the water heater to permit servicing
of the water heater. Compounds used on the threaded joints of the gas
piping must be resistant to the action of liquefied petroleum gases/propane
gas. DO NOT apply pipe dope to the gas valve inlet and make certain that
no pipe dope has become lodged in the inlet screen of the gas valve.
Extreme care must be taken to ensure no pipe dope enters the gas valve.
Avoid excessive torque when tightening the gas supply line to the gas
valve. Excessive torque may result in cracking of the gas valve housing
and could create a gas leak. The suggested maximum torque is 31.5 ft. lbs.
(4.4 kg-m).
2. This water heater and its gas connection must be leak tested before placing
the water heater in operation. Check for gas leaks with a soap and water
solution and a brush or a commercial leak detector fluid. NEVER USE A
MATCH OR OPEN FLAME FOR TESTING!
WARNING
Prior to connecting the gas supply line to a gas fired water heater,
ensure that the gas supply line does not have moisture/water or
dirt/scale inside the gas line. Commonly this check is done at the lowest
point in the gas distribution system prior to gas burning appliances.
WARNING
The manufacturer of this water heater will not be liable for any damage
or injury caused as a result of a cracked gas inlet as a result of
excessive torque.