Installation and Operation Instructions Document 1258C Installation and Operation Instructions for Brute Elite Modulating Boiler Model BNTH Sizes 080–850 MBTU/h Water Heater Model BNTV Sizes 150–850 MBTU/h FOR YOUR SAFETY: This product must be installed and serviced by a professional service technician, qualified in hot water boiler and heater installation and maintenance.
BRADFORD WHITE CORP. Table of Contents Section 1 General Information 1.1 1.2 1.3 1.4 1.5 1.6 Introduction........................................................ 1 Model Identification............................................ 1 Appliance Overview........................................... 2 Warranty............................................................ 6 Unpacking.......................................................... 6 Dimensions........................................................
BRUTE ELITE Section 9 First Start-Up and Adjustment Instructions 9.1 9.2 9.3 9.4 9.5 Filling the Boiler System.................................. 50 First Operation................................................. 50 Adjusting the Differential and Manifold Pressure............................................ 51 Shutting Down the NeoTherm Unit.................. 53 Restarting the NeoTherm Unit......................... 53 Section 12 Replacement Parts 13.1 13.
BRADFORD WHITE CORP.
Page 1 BRUTE ELITE Section 1 GENERAL INFORMATION All installations must be made in accordance with 1) American National Standard Z223.1/NFPA54-Latest Edition “National Fuel Gas Code” or 2) CSA B149.1 “Natural Gas and Propane Installation Code” and with the requirement of the local utility or other authorities having jurisdiction. Such applicable requirements take precedence over the general instructions contained herein.
Page 2 BRADFORD WHITE CORP. 1.3 Appliance Overview - See Figures 1 through 7.
Page 3 BRUTE ELITE EXHAUST VENT CONNECTION AIR INLET CONNECTION GAS CONNECTION WATER INLET WATER OUTLET PRESSURE RELIEF VALVE USER CONTROL INTERFACE AIR PRESSURE SWITCH ON / OFF SWITCH HEAT EXCHANGER DRAIN VALVE CONDENSATE TRAP VENTURI GAS VALVE AIR TRANSITION AIR/ GAS BLOWER Figure 3 - Location of Components, Size 285 EXHAUST VENT CONNECTION PRESSURE RELIEF VALVE WATER INLET WATER OUTLET GAS CONNECTION USER CONTROL INTERFACE AIR INLET CONNECTION ON / OFF SWITCH HEAT EXCHANGER MANUAL SHUTOFF G
Page 4 BRADFORD WHITE CORP.
BRUTE ELITE Page 5 GAS CONNECTION WATER INLET PRESSURE RELIEF VALVE EXHAUST VENT CONNECTION AIR INLET WATER OUTLET USER CONTROL INTERFACE ON / OFF SWITCH GAS VALVE VENTURI DRAIN VALVE AIR/ GAS BLOWER HEAT EXCHANGER MANUAL SHUTOFF GAS VALVE CONDENSATE TRAP Figure 7 - Location of Components, Sizes 750 and 850
Page 6 BRADFORD WHITE CORP. 1.4 Warranty Bradford White appliances are covered by a limited warranty. All warranty claims must be made to an authorized Bradford White wholesale rep / distributor. To find information about the wholesalers in your area, please go to www.bradfordwhite.com. and click on ‘Wholesalers’. Claims must include the serial number and model (this information can be found on the rating plate), installation date, and name of the installer.
Page 7 BRUTE ELITE W SIZE IN L IN CM H CM IN AIR INLET VENT CM IN CM IN CM 80 25 64 19½ 49 38¼ 97 2 5.1 2 5.1 105 25 64 19½ 49 38¼ 97 2 5.1 2 5.1 150 25 64 19½ 49 38¼ 97 3 7.6 3 7.6 199/210 25 64 26¾ 68 38¼ 97 3 7.6 3 7.
Page 8 BRADFORD WHITE CORP. Section 2 LOCATING THE APPLIANCE 2.1 General Information The Brute Elite unit is designed for indoor installations only. The appliance should be located to provide clearances on all sides for maintenance and inspection. It should not be located in an area where leakage of any connections will result in damage to the area adjacent to the appliance or to lower floors of the structure.
Page 9 BRUTE ELITE Section 3 VENTING AND COMBUSTION AIR Method 1: Two permanent openings, one commencing within 12” (300mm) of the top and one commencing within 12” (300mm) of the bottom, of the enclosure shall be provided. The openings shall communicate directly, or by ducts, with the outdoors or spaces that freely communicate with the outdoors.
Page 10 BRADFORD WHITE CORP. Other methods of introducing combustion and ventilation air are acceptable, providing they conform to the requirements in the applicable codes listed above. In Canada, consult local building and safety codes or, in absence of such requirements, follow CAN/CSA B149. Ducted Combustion Air The combustion air can be taken through the wall, or through the roof.
Page 11 BRUTE ELITE All installations should be done following the vent supplier’s recommended installation techniques. If manufacturer’s instructions are not available for the material used, follow the Bradford White recommendations. The vent pipe must pitch upward, toward the vent terminal, not less than 1/4” per foot, so that condensate will run back to the Brute Elite to drain. Route vent pipe to the heater as directly as possible.
Page 12 included with the Brute Elite and shown in the Unpacking section, be installed. Be sure to install and terminate both vent and combustion air pipes per the Venting and Combustion Air section of the Brute Elite instructions. BRADFORD WHITE CORP. damage by accident or vandalism. It must be at least 7 feet (2.1m) above a public walkway. 3. Locate the combustion air terminal so that it cannot be blocked by snow.
Page 13 BRUTE ELITE U.S. Installations (see note 1) Canadian Installations (see note 2) A= Clearance above grade, veranda, porch, deck, or balcony 12 inches (30 cm) See note 6 12 inches (30 cm) See note 6 B= Clearance to window or door that may be opened Direct vent only: 12 inches (30cm); Other than Direct vent: 4 ft (1.
Page 14 BRADFORD WHITE CORP. a. In the event that the side-wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard-wired carbon monoxide with alarm and battery back-up may be installed on the next adjacent floor level. b.
Page 15 BRUTE ELITE 3.4 Common Vent Test NOTE: This section does not describe a method for common venting Brute Elite units. It describes what must be done when a unit is removed from a common vent system. Brute Elite units require special vent systems and fans for common vent. Contact the factory if you have questions about common venting Brute Elite units.
Page 16 BRADFORD WHITE CORP. Brute Elite NATURAL GAS REQUIRED SIZE CU FT / HR. 80 105 150 80 105 150 199/210 199/210 285 399 500 600 750 285 399 500 600 750 850 850 Section 5 PUMP REQUIREMENTS TO SIZE PIPING: Measure linear distance from meter outlet to last boiler. Add total input of all boilers and divide by 1000 to obtain cu ft / hr required. Add total equivalent length of fittings used according to Table 6B.
Page 17 BRUTE ELITE Section 6A WATER CONNECTIONS BNTH BOILER Section 6 is divided into two parts. Section 6A covers BNTH units designed for hydronic heating. Section 6B covers BNTV models, which are designed exclusively for “volume water” domestic hot water applications. Refer to the proper section for instructions on installing and piping your product. Refer to Table 9 for the connection pipe sizes required. 6A.
Page 18 6A.3 Condensate Drain A condensate drain trap is built into the Brute Elite unit. Connect a 3/4” PVC pipe between the drain connection and a floor drain (or a condensate pump if a floor drain is not accessible). The condensate drain must be installed so as to prevent accumulation of condensate. When a condensate pump is not used, the tubing must continuously slope downward toward the drain with no spiraling. Consult local codes for the proper disposal method for the condensate.
Page 19 BRUTE ELITE Brute Elite Figure 15 - Hydronic Piping — Single Boiler, Zoning with Circulators
Page 20 BRADFORD WHITE CORP.
Page 21 BRUTE ELITE Brute Elite Brute Elite Figure 17 - Hydronic Piping — Multiple Boilers, Zoning with Circulators
Page 22 BRADFORD WHITE CORP.
Page 23 BRUTE ELITE Brute Elite Brute Elite Brute Elite Brute Elite Figure 19 - Hydronic Piping — Multiple Boilers, Reverse Return, Multi-Temp Zones, Zoning with Circulators
BRADFORD WHITE CORP. Brute Elite Page 24 Figure 20 - Hydronic Piping — Heating Zones with Indirect DHW Tank Piped with Zone Pumps The indirect DHW tank is piped directly off of the boiler. The boiler pump must shut down during DHW operation.
Page 25 Brute Elite Brute Elite Brute Elite BRUTE ELITE Figure 21 - Hydronic Piping, Multiple Boilers with Indirect DHW Off of One Boiler The boiler pump must shut down during DHW operation.
Page 26 Section 6B WATER CONNECTIONS BNTV WATER HEATER Section 6 is divided into two parts. Section 6A covers BNTH units designed for hydronic heating. Section 6B covers BNTV models, which are designed exclusively for “volume water” domestic hot water applications. Refer to the proper section for instructions on installing and piping your product. Refer to Table 9 for the connection pipe sizes required. 6B.
Page 27 BRUTE ELITE 6B.3 Cold Water Make-Up 6B.5 Freeze Protection The cold water make-up may be connected to the tank or to the inlet of the boiler as shown in Figures 22-25. Install back flow preventers and shut offs where needed or required by code. Pipe sizes may have to be increased to accomodate cold water make-up flow. Brute Elite heaters are not certified for outdoor installation, so the chance of freezing is minimized.
Page 28 BRADFORD WHITE CORP. NOTES: 1. Optional CWMU & Recirc. line location. 2. Locate BNTV DHW sensor or remote aquastat well in lower 1/3 of tank. 3. Back flow preventer may be required - check local codes. 4. Thermal expansion tank may be required - check local codes. 5. Factory mounted pumps are sized for a max pipe length of 30’ total, 6-90° elbows, full pipe size. 6. Caution: Pump sizing must be based on water hardness at job site.
Page 29 BRUTE ELITE NOTES: 1. Optional CWMU & Recirc. line location. 2. Locate BNTV DHW sensor or remote aquastat well in lower 1/3 of tank. 3. Back flow preventer may be required - check local codes. 4. Thermal expansion tank may be required check local codes. 5. Factory mounted pumps are sized for a max pipe length of 30’ total, 6-90° elbows, full pipe size. 6. Caution: Pump sizing must be based on water hardness at job site. WARNING: This drawing shows suggested piping configuration and valving.
Page 30 BRADFORD WHITE CORP. Section 7 THE USER INTERFACE The Brute Elite ‘User Interface’ was updated for the 2013 model year to the User Interface shown in this manual. 7.
Page 31 BRUTE ELITE • Press “I” Info/Install button 7.2 Navigating the User Interface • Scroll to highlight “Display Setup”, press OK Navigating into the Display area menus is as easy as it looks. The Info/Install button will be the primary button that you will use to start, and the OK button is what you press to select and approve the parameters that you have set on the Display. The arrow keys are for moving up and down, left and right within the menus.
Page 32 BRADFORD WHITE CORP. Quick Start This menu gives you an easy way to check or change the most common settings on the unit: • CH setpoint • DHW setpoint • Outdoor reset • Low water temperature • Maximum outdoor temperature • Minimum outdoor temperature • Adjustable high limit • Adjustable low limit See Section 8B for more information. Login If you want to change a setup value or function, and the system requires a password, you can enter it here. See the section on “Login Display.
Page 33 BRUTE ELITE • You can change the numbers in the other boxes in the same way. • When the new setting is correct, press the round OK button. Entering a Password or Name The system uses a different type of screen to enter a password or name. If you want to change a setup value or function, and the system requires a password, you can enter it using the Login screen. See Fig. 31. Fig. 29 – Changing a Value • The current setting for the setpoint appears in the box at the top of the screen.
Page 34 BRADFORD WHITE CORP. changed by a trained technician who enters a password. These include setup and parameter changes made when the system is installed, and some diagnostic and troubleshooting functions. The installer level password is “lnt” (lower case “LNT”). OEM Level Changing a Value Using a “Slider” There is another type of control screen you may see. This type of screen uses a “slider” to set the value. This system is used on the LCD Contrast screen (available under Display Setup.) See Fig.
Page 35 BRUTE ELITE Section 8A QUICK START MENU Section 8 is divided into three parts. Section 8A includes instructions for using the Quick Start Menu. Section 8B covers basic installation and wiring. Section 8C includes more detailed setup instructions and wiring diagrams. Outdoor Reset Functions The next four lines in the display are used to set up the Outdoor Reset functions: • Outdoor Reset Enable/Disable - Note: This function can be Enabled/Disabled only by a factory trained technician.
Page 36 BRADFORD WHITE CORP. Section 8B BASIC INSTALLATION AND WIRING Section 8 is divided into three parts. Section 8A includes instructions for using the Quick Start Menu. Section 8B covers basic installation and wiring. Section 8C includes more detailed setup instructions and wiring diagrams. 8B.
Page 37 BRUTE ELITE Caution The supply voltage to the Brute Elite unit must not be disconnected, except for service or isolation, or unless otherwise instructed by procedures outlined in this manual. To signal a call for heat, use the 24V field interlock, as shown in the wiring diagram. DO NOT MAKE AND BREAK THE LINE VOLTAGE TO THE Brute Elite UNIT TO SIGNAL A CALL FOR HEAT. A call for heat/ end call for heat MUST be connected to the field interlock terminals.
Page 38 BRADFORD WHITE CORP. Section 8C DETAILED SETUP INSTRUCTIONS and DIAGRAMS Section 8 is divided into three parts. Section 8A includes instructions for using the Quick Start Menu. Section 8B covers basic installation and wiring. Section 8C includes more detailed setup instructions and wiring diagrams. 8C.1 24 VAC Transformer with Integral Circuit Breaker 24Vac is supplied by a transformer mounted underneath the control panel.
Page 39 BRUTE ELITE • As the temperature begins to rise above 32°F, the Outdoor Reset function causes the setpoint to be lowered. At these warmer temperatures, the heating load on the system is not as great, so the system does not have to reach as high a temperature to handle the load. • As you can see from the display, at an outdoor temperature of about 70°F, the system stops adjusting the setpoint. Above 70°F, the setpoint is constant at 100°F (or another value that you choose).
Page 40 BRADFORD WHITE CORP. “CH Configuration.” Select “Warm Weather Shutdown.” On the line for “Warm Weather Shutdown,” select “Immediately.” then go to “CH Configuration.” Select “Outdoor Reset Configuration.” Set the value on the line for “Min. Boiler Water Temp.” If your system has more than one boiler, and is controlled using the Lead/ Lag function – How to get there: From the “Home” screen, press “I” to go to “Info/ Install.” Choose “Advanced Setup,” then go to “Lead/ Lag Configuration.
Page 41 BRUTE ELITE DHW Temperature Setting Regardless of the type of DHW setup, the setpoint adjustment is made the same way. How to get there: From the “Home” screen, press “I” to go to “Info/ Install.” Choose “Advanced Setup,” then go to “DHW Setpoint.” Hydronic Heating with Domestic Hot Water (DHW) Priority When using the Brute Elite for hydronic heating with domestic hot water priority, a call for heat must be supplied to the “T-T or Interlock” terminal.
Page 42 BRADFORD WHITE CORP. Boiler Pump Interrupt Function The Boiler pump interrupt feature is used in some applications when the boiler is being used for both hydronic and domestic hot water heating. The interrupt jumper is used to turn off the boiler pump during a domestic hot water demand. For this to work properly the system must be plumbed and pumped to allow the DHW pump to supply the flow and head requirements for both the boiler and indirect water heater.
Page 43 BRUTE ELITE Boiler 1 Boiler 2 Boiler 3 Boiler 4 Display Controller Burner Fig. 38 – “Lead/Lag” Operation in a System with Four Boilers. Note - the Displays on Boilers 2 thru 4 will display information pertaining only to that specific boiler. Central Heat setpoint. (Actually this is the LL CH setpoint less the On Hysteresis value. The default setting for On Hysteresis is 5°F, but this is adjustable.
Page 44 BRADFORD WHITE CORP.
Page 45 BRUTE ELITE Boiler 1 Boiler 2 Boiler 3 Boiler 4 MB 1 MB 2 MB 1 MB 2 MB 1 MB 2 MB 1 MB 2 A B C A B C A B C A B C A B C A B C A B C A B C User interface User interface User interface User interface Figure 40 - Lead-Lag / Cascading Wiring Connections Wiring Connections for Lead/Lag Now you can make the Modbus wiring connections between the units. The controller in each boiler includes two wiring terminals for the Modbus system, labeled “MB1” and “MB2.
Page 46 BRADFORD WHITE CORP. 8C.10 Optional Field Connections Terminal block 8 (TB8) in the control panel can be used for connecting optional components, such as low water cutoffs, flow switches, additional high limits and other field-supplied devices that must be interlocked with the boiler. These are non-powered dry contacts only. All safeties or end switches must be wired in series by removing the supplied jumpers.
Page 47 BRUTE ELITE 8C.12 Ladder and Wiring Diagrams (See Figures 43 through 45.) WARNING When servicing the controls, label all wires prior to disconnection. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.
Figure 44 - Wiring Diagram, All Sizes (with standard EMEA display) ALARM BLK/OR ALARM WH/GY WH/OR H2354300B Y = YELLOW SYSTEM SENSOR WH = WHITE BL TN = TAN GR/VT BL/Y GAS VALVE PIN NO. 1 2 3 4 80-285 Y DKB GN 399-500 BR BL NA TABLE 2 - GAS VALVE WIRE COLORS TABLE 2.
Y WH/GY Figure 45 - Wiring Diagram, All Sizes - with Optional Full-Color Touchscreen H2355400B Y = YELLOW WH/OR WH = WHITE ALARM GAS VALVE PIN NO.
Page 50 BRADFORD WHITE CORP. Section 9 FIRST START-UP AND ADJUSTMENT INSTRUCTIONS 14. Prime the condensate trap with water. (This is not required for BNTH 600, 750, and 850 units.) 15. Refer to local codes and the make-up water valve manufacturer’s instructions as to whether the make-up water valve should be left open or closed. 9.1 Filling the Boiler System 16. After placing the unit in operation, the ignition system safety shutoff device must be tested. 1. 2.
Page 51 BRUTE ELITE How to get there: From the “Home” screen, press “I” to go to “Info/ Install.” Choose “Test,” then go to “Forced Rate.” Select “Set High Fire,” then select “Start Test.” label and turn on the gas and electrical power to the appliance. 4. The Brute Elite unit will begin the start sequence. The blower and pump will energize for the pre-purge period, then the ignition sequence will start. After all safety devices have been verified, the gas valve will open.
Page 52 BRADFORD WHITE CORP.
Page 53 BRUTE ELITE 9.4 Shutting Down the Brute Elite Unit 1. Turn off the main electrical disconnect switch. 2. Close all manual gas valves. 3. If you think the Brute Elite unit might freeze, drain it. All water must be removed from the heat exchanger, or damage from freezing may occur. Also be sure to protect the piping in the building from freezing. Caution This step must be performed by a qualified service person. 9.
Page 54 Section 10 MAINTENANCE WARNING Disconnect all power to the appliance before attempting any service. Contact with electricity can result in severe injury or death. 10.1 System Maintenance Do this once a year, unless otherwise noted. 1. Lubricate the system water-circulating pump, if required, per the instructions on the pump. 2. If a strainer is employed in a pressure reducing valve or the piping, clean it every six moBNTHs. 3.
Page 55 BRUTE ELITE the control. If control replacement is required, turn off all power to the appliance and shut off all manual gas valves to the appliance. Remove the front door to the appliance and the plastic bezel and the control panel. Remove all wire connections from the control board. The control board connections are keyed to only allow connection in the proper location, but proper handling techniques should be used to avoid damage to the wiring or connectors.
Page 56 Transformer with Integral Circuit Breaker The appliance has a 24Vac transformer with integral 4 amp circuit breaker installed to supply the control voltage required for the appliance. The transformer is sized to provide power for the Brute Elite unit only, and should not be used to supply power to additional field devices. If additional loads are added, or a short occurs during installation, the integral circuit breaker may trip.
Page 57 BRUTE ELITE 12. Place the appliance in operation according to the instructions in Section 10. Check all gas connections for leaks. Confirm that all fasteners are tight. NT size (mbtu) Kit number 80 CA006201 105 CA006202 Optional Gas Pressure Switches 150 CA006203 The high and low gas pressure switches are 24V manual reset switches that act to cut power to the gas valves if the gas pressure is too low or too high for proper operation.
Page 58 Section 11 OPERATING DETAILS AND TROUBLESHOOTING 11.1 BRADFORD WHITE CORP. 5. There is a pre-ignition time of two seconds to check the flame sensor operation and status. During this period an intermittent spark can be seen. 6. Next there is a trial for ignition period of four seconds. The direct spark ignition switches to constant spark for three seconds. During this time the gas valve is open.
Page 59 BRUTE ELITE 11.5 Anti-Short-Cycle (ASC) Because the Brute Elite unit is a modulating boiler, and its input will decrease when there is a reduction in the heating load, short cycling is greatly reduced. If the heating load drops below the minimum input of the boiler for an extended period, the boiler will have a tendency to short cycle. This can be a symptom of improper control strategy or setpoints, or a load distribution problem.
SIZE BNTH 80 SIZE BNTH 105 SIZE BNTH 150 BNTV 150 SIZE BNTH 210 BNTV 199 SIZE BNTH 285 BNTV 285 Front Panel Handle Rear Panel Left Side Panel 2 3 4 R8D3002 R50D3101 R50D3204 R60D3200 R10D3002 R50D3101 R50D3204 R60D3200 R15D3002 R50D3101 R50D3204 R60D3200 R19D3002/ R50D3101 R50D3204 R60D3200 Left Top Panel Middle Left Top Panel Middle Right Top Panel Right Top Panel Jacket Angle Support 6 7 7A 8 9 R50D7122 R50D7120 R50D3003 Jacket Support, Left Stanchion Jacket Support
R50D1005 20D1005 R15D1002 20D1007 20D1005 R15D1002 SIZE BNTH 150 BNTV 150 20D1007 20D1005 R40D1001 SIZE BNTH 210 BNTV 199 PVC Reducer RD2010501 — R20D4020 R20D4020 RD2010501 — RP2065600 RP2053000 RP2065600 RP2053000 R50D4020 R50D4020 — — — — — Gas Valve Flange Kit Gas Valve/Venturi Cork Gasket Gas Valve O-Ring Venturi O-Ring 46 47 48 — R30-227 — — R30-227 — — — R30-227 — — — R30-227 — — — — R30-227 — — — RS2105200 — — — — RS2105200 — RS2104900 R
Duct/Venturi Transition Gas Supply Pipe Gas Pipe, 3/4” NPT Formed Nipple Air Inlet Flex Hose Air Inlet Collector Electrical Connector w/Cable — Elbow Adapter Blower Gasket W/Fasteners — 51 52 53 55 56 57 58 59 RS2106900 RS2105500 RS2105800 — — — — RD0091403 — RP2051400 — — — — D0091401 — RP2051400 R10D5013 — — SIZE BNTH 210 BNTV 199 Duplex Outlet Water Temperature Sensor Duplex Stack Temperature Sensor Pressure Relief Valve, BNTH 64 65 66 (30 PSI) RS2108500 69 RS
RS2109100 Main Burner w/gasket Flame Sensor w/gasket R2069200 Ignitor w/gasket 72 73 74 RW2013400 74C Flame/Sensor Gasket Sight Glass 77 R50D2020 R10-143 RS2109400 (5) R50D2020 R10-143 RS2109400 (5) RS2108600 RW2013400 m4-.7X8mm S2112700 RW2013300 R2069300 R2069200 R2069102 R50D2021 RT2109000 RS2109100 R50D2020 R10-143 RS2109400 (5) RS2108600 RW2013400 m4-.
Page 64 BRADFORD WHITE CORP.
BRUTE ELITE Figure 51a - Internal Components, Sizes 80–210 Page 65 Figure 51b - Internal Components, Sizes 285–600
Page 66 Figure 51c - Internal Components, Sizes 750-850 BRADFORD WHITE CORP.
BRUTE ELITE Figure 52a - Gas Train Components, Sizes 80-500 Page 67
Page 68 Figure 52b - Gas Train Components, Sizes 600-850 BRADFORD WHITE CORP.
BRUTE ELITE Figure 53 - Heat Exchanger Components Page 69
Page 70 Figure 54 - Electrical Components BRADFORD WHITE CORP.
Page 71 BRUTE ELITE Appendix A SOFTWARE CONTROL FUNCTIONS This table includes a listing of all of the control functions that can be used by the operator or installer. Functions that require a password are indicated in the second column. Name PW? Function How to get there Adjustable high limit Y The absolute high limit for the water outlet is pre-set at the factory. If desired, you can set a lower value here.
Page 72 BRADFORD WHITE CORP. Name PW? Function How to get there Demand switch (CH) - Set to “STAT terminal.” Info/ Advanced Setup/ CH Configuration DHW pump control Y The boiler pump can be turned on manually, or it can be set to operate automatically. Info/ Test/ Manual Pump Operation A new value can be written here if the pump or controller is replaced. Info/ Advanced Setup/ System Config./ Statistics Config.
Page 73 BRUTE ELITE Name PW? Max. outdoor temp. (CH) - Max. outdoor temp. (LL) - Function How to get there Used with Outdoor Reset – Quick Start This is the maximum outdoor temperature at which the Outdoor Reset feature will be active. Above this point, the Low Water Temp. will be used as the setpoint. Info/ Advanced Setup/ CH Configuration/ Outdoor Reset Config.
Page 74 BRADFORD WHITE CORP. Name PW? Function How to get there Off hysteresis (DHW) - When producing Domestic Hot Water – Info/ Advanced Setup/ DHW Configuration The control system will not shut off the boiler until the temperature at the System sensor rises to the DHW setpoint plus a hysteresis value (normally about 10°F). Off hysteresis (LL) - When using the Lead/ Lag system to control multiple boilers – Info/ Advanced Setup/ Lead Lag Configuration/ LL Master Config.
Page 75 BRUTE ELITE Name PW? Function How to get there Pump exercise interval Y The system can be set to exercise the pumps at set intervals. Enter a non-zero value to turn on the function. Info/ Advanced Setup/ System Config./ Pump Config. Pump exercise time Y If the pump exercise feature is enabled, this value sets the length of time that each pump will be exercised. Info/ Advanced Setup/ System Config./ Pump Config.
Page 76 BRADFORD WHITE CORP. Appendix B ERROR MESSAGES This table includes a listing of the faults that might be generated by the controller, and displayed on the Operator Interface. Some of these can be corrected by an installer changing a parameter, while other conditions are more complicated, and will require a service technician. The first column lists the code number that will appear at the beginning of the Lockout or Hold message. The second column lists a short description of the condition.
Page 77 BRUTE ELITE Code Description L or H Procedure 12 Internal fault: H Internal fault Safety relay drive cap short 1. Reset module 2. If fault repeats, replace module. 13 Internal fault: H or L PII (Pre-Ignition Interlock) shorted to ILK (Interlock) 15 Internal fault: 1. Reset module 2. If fault repeats, replace module. L Safety relay test failed due to feedback ON 16 Internal fault: Internal fault: 2. If fault repeats, replace module. L Internal fault: 2.
Page 78 BRADFORD WHITE CORP. Code Description L or H Procedure 27 Internal fault: H Internal fault Flame rod shorted to ground detected 28 Internal fault: 1. Reset module 2. If fault repeats, replace module. H A/D linearity test fails Internal fault 1. Reset module 2. If fault repeats, replace module. 29 Internal fault: H Flame bias cannot be set in range 30 Internal fault: 1. Reset module 2. If fault repeats, replace module.
Page 79 BRUTE ELITE Code Description L or H Procedure 63 LCI (Limit Control Input) OFF H 1. Check wiring and correct any faults. (Safety Chain Open) 2. Check Interlocks connected to the LCI to assure proper function. 3. Reset and sequence the module; monitor the LCI status. 4. If code persists, replace the module 64 PII (Pre-Ignition Interlock) OFF H or L 1. Check wiring and correct any faults. 2. Check Preignition Interlock switches to assure proper functioning. 3. Check the valve operation.
Page 80 BRADFORD WHITE CORP. Code Description L or H Procedure 94 Header sensor fault H 1. Check wiring and correct any possible errors. 2. Replace the header sensor. 3. If previous steps are correct and fault persists, replace the module. 95 Stack sensor fault H 1. Check wiring and correct any possible errors. 2. Replace the stack sensor. 3. If previous steps are correct and fault persists, replace the module. 96 Outdoor sensor fault H 1. Check wiring and correct any possible errors. 2.
Page 81 BRUTE ELITE Code Description L or H Procedure 108 Flame lost in run L 1. Check main valve wiring and operation - correct any errors. 2. Check the fuel supply. 3. Check fuel pressure and repeat turndown tests. 4. Check ignition transformer electrode, flame detector, flame detector siting or flame rod position. 5. If steps 1 through 4 are correct and the fault persists, replace the module. 109 Ignition failed L 1. Check the main valve wiring and operation - correct any errors. 2.
Page 82 BRADFORD WHITE CORP. Code Description L or H Procedure 132 Fan speed failed during run H 1. Check wiring and correct any potential wiring errors. 2. Check the VFDs (Variable-speed Fan Drive) ability to change speeds. 3. Change the VFD 4. If the fault persists, replace the module. 137 ILK (Interlock) failed to close H 1. Check wiring and correct any possible shorts. 2. Check Interlock (ILK) switches to assure proper function. 3.
Page 83 BRUTE ELITE Code Description L or H Procedure 159 Main valve Off L 1. Check the main valve terminal wiring and correct any errors. 2. Reset and sequence the module. If fault persists, replace the module. 160 Ignition On L 1. Check Ignition terminal wiring and correct any errors. 2. Reset and sequence the module. If fault persists, replace the module. 161 Ignition Off L 1. Check the ignition terminal wiring and correct any errors. 2. Reset and sequence the module.
Page 84 BRADFORD WHITE CORP. Code Description L or H Procedure 187 Invalid DHW (Domestic Hot Water) high limit enable setting L 1. Recheck selected parameters, reverify and reset module. 2. If fault repeats, verify electrical grounding. 3. If fault repeats, replace module. 188 Invalid DHW (Domestic Hot L Water) high limit response setting 1. Recheck selected parameters, reverify and reset module. 2. If fault repeats, verify electrical grounding. 3. If fault repeats, replace module.
Page 85 BRUTE ELITE Code Description L or H Procedure 204 Invalid NTC sensor type setting L 1. Recheck selected parameters, reverify and reset module. 2. If fault repeats, verify electrical grounding. 3. If fault repeats, replace module. 205 Invalid Outlet high limit response setting L Invalid PII (Pre-Ignition Interlock) enable setting L Invalid Postpurge time setting L 1. Recheck selected parameters, reverify and reset module. 2. If fault repeats, verify electrical grounding. 3.
Page 86 BRADFORD WHITE CORP. Code Description L or H Procedure 222 Unconfigured Outlet high limit setpoint setting L 1. Recheck selected parameters, reverify and reset module. Unconfigured Stack limit setpoint setting L Invalid DHW (Domestic Hot Water) demand source setting L Invalid Flame threshold setting L 2. If fault repeats, verify electrical grounding. 3. If fault repeats, replace module. 223 1. Recheck selected parameters, reverify and reset module. 2.
Page 87 BRUTE ELITE Code Description L or H Procedure 237 Invalid DHW (Domestic Hot Water) connector type setting L 1. Recheck selected parameters, reverify and reset module. Invalid Stack connector type setting L 2. If fault repeats, verify electrical grounding. 3. If fault repeats, replace module. 238 1. Recheck selected parameters, reverify and reset module. 2. If fault repeats, verify electrical grounding. 3. If fault repeats, replace module.
H2357200C Dimensions and specifications subject to change without notice in accordance with our policy of continuous product improvement. Ambler, PA 19002 Tech. Service (800) 334-3393 Service Parts (800) 538-2020 Warranty Service (800) 531-2111 www.BradfordWhite.com Litho in U.S.A.