Installation / Operation Instruction Manual
Page 46
B
RADFORD
W
HITE
Figure 33. Power & Control Panel Layout
NOTE: All water heating units are shipped from the factory with a resistor (jumper) between
the outdoor sensor terminals (terminals 1 and 2 on TB7). If this resistor is removed,
the water heater will not be able to heat water above 140°F.
Factory
installed
100Ω resistor
on water
heaters
7.B.2 Variable Speed Pump Control
Variable speed pump control is optional equipment on all
commerical Brute boilers. Pump speed is controlled to
maintain a user-chosen temperature rise between the inlet
and outlet of the unit.
The variable speed pump control will operate the boiler
pump at maximum ow during boiler startup to ensure
stable operation is reached before introducing variable
water ow. This key feature keeps the boiler’s combustion
and variable speed pump’s ow in phase with each other,
protecting the heat exchanger from potential low ow
conditions.
Contact your manufacturers representative for more
details.