Installation / Operation Instruction Manual
Page 28
B
RADFORD
W
HITE
the responsibility of the property owner to secure
the services of qualied licensed professionals
for installation of hard-wired carbon monoxide
detectors.
a. In the event that the side-wall horizontally vented
gas fueled equipment is installed in a crawl space
or an attic, the hard-wired carbon monoxide with
alarm and battery back-up may be installed on the
next adjacent oor level.
b. In the event that the requirements of the
subdivision cannot be met at the time of completion
of installation, the owner shall have a period
of thirty (30) days to comply with the above
requirements, provided, however, that during said
thirty (30) day period, a battery operated carbon
monoxide detector with an alarm be installed.
2. Approved Carbon Monoxide Detectors
Each carbon monoxide detector shall comply with
NFPA 720 and be ANSI/UL 2034 listed and IAS
certied.
Figure 21. Multiple Side-Wall Terminals,
IMPORTANT: Terminals must be place such that they remain a
minimum of 12” above the expected snow line. Local codes may
have more specific requirements and must be consulted. Refer to the
NFPA 54 National Fuel Gas Code and your local codes for all
required clearances for venting.
3. Signage
A metal or plastic identication plate shall be
permanently mounted to the exterior of the building
at a minimum height of eight (8) feet above grade
directly in line with the exhaust vent terminal for
horizontally vented gas fueled heating appliance or
equipment. The sign shall read, in print no less than
one-half (1/2) inch in size: “GAS VENT DIRECTLY
BELOW, KEEP CLEAR OF ALL OBSTRUCTIONS.”
4. Inspection
The state or local gas inspector of the side-wall
horizontally vented gas fueled appliance shall not
approve the installation unless, upon inspection, the
inspector observes carbon monoxide detectors and
signage installed in accordance with the provisions of
248 CMR 5.08(2)(a) 1-4.