Brute
HIGH EFFICIENCY COMMERCIAL BOILERS AND VOLUME WATER HEATERS
8.7.1 through 8.7.15 are the
Con guration Sub-Menus.
The Con guration Sub-Menus ( ALL 18 )
8.7. 1
__
18
Some of these con gurations will require a Login
rst. See Menu 3 on page 46
8.7.2 B Setting Up 4-20 mA Setpoint
The Central Heat Con guration Menu (Menu 18) has
three sub-menus and each of them can be reached
by scrolling left or right thru the arrows on the left
and right. See Menu 19. The three sub-menus are
‘Central Heat’, ‘Setpoint’, and ‘Modulation’.
To set up 4-20 mA Setpoint, you will need to go
into the ‘Setpoint’ sub-menu fi rst and change the
Setpoint source from Local to S2 (J8-6) 4-20 mA.
Then go to the ‘Modulation’ sub-menu and set the
Modulation source to Local. Both Setpoint and
Modulation cannot have their source set as Local.
From the Central Heat Con guration Sub-Menu,
choose either the left or right arrow.
then Click onto ‘Local’.
Click onto the down arrow to see further options.
When using the Brute for hydronic heating, a call for
heat must be supplied to the “T-T” terminals found on
TB7 labeled “T-T or Interlock”. Once a call for heat
is established, the control will start the appropriate
(selected) pumps, and begin the ignition process.
8.7.1 System Identi cation & Access
This sub-menu will display information regarding
software, date codes, model numbers and program
name, as well as giving the installer access to re-name
the boiler and to change the modbus addresses for lead
lag operation.
Press the back arrow on the top right corner of the
screen to return to the ‘Con guration Menu’.
8.7.2 A CH - Central Heat Con guration
Menu 18. The Con guration Menu
Make sure that CH is Enabled and then press one of the
black arrows (either side) to get to the Set-Point screen.
Press on the ‘Setpoint’ box to make adjustments
to setpoint, and modulation for a single boiler CH
demand.
until you are on the ‘Setpoint’ sub-menu,
Menu 19. The Setpoint submenu
There are 18 total Conguration Sub
Menus. Please see the Installation and