Submittal
Sizing Data
Input Output Thermal Gas Conn. Water Shipping
Model Efciency Size Conn.Size Weight
BTU/h kW BTU/h kW % inches inches lbs
kg
NTV 150 150,000 44.0 142,500 41.7 95 ½ NPT 1¼ NPT 228 103
NTV 199 199,000 58.3 193,030 56.5 97 ½ NPT 1¼ NPT 270 123
NTV 285 285,000 83.5 270,750 79.3 95 ¾ NPT 2 NPT 299 136
NTV 399 399,000 116.9 383,040 112.2 96 ¾ NPT 2 NPT 364 165
NTV 500 500,000 146.5 480,000 140.6 96 1 NPT 2 NPT 419 190
NTV 600 600,000 175.8 582,000 170.4 97 1 NPT 2 NPT 426 193
NTV 750 750,000 219.8 705,000 206.4 94 1½ NPT 2 NPT 481 218
NTV 850 850,000 249.1 816,000 238.9 96 1½ NPT 2 NPT 503 228
Clearances
Suggested Service
Appliance Access Clearance
Surface inches cm
Left Side 1 2.5
Right Side 12 31
To p 24 61
Back 6 15
Closet, Front 6 15
Alcove, Front 24 61
Vent – –
CertiedbyCSAforzeroclearancetocombustiblematerialsonallsides.
Accessories
for Field
Mounting
Vent System
Intake (Air) Exhaust (Vent) Maximum Allowable
Size Pipe Pipe Equivalent Length*
150 3" 3" 100 ft 30 m
199 3" 3" 100 ft 30 m
285
3" 3" 20 ft 6.1 m
4" 4" 100 ft 30 m
399
4" 4" 100 ft 30 m
500
4" 4" 100 ft 30 m
600
4" 4" 40 ft 12 m
**6"** **6"** 100 ft 30 m
750
4" 4" 40 ft 12 m
6" 6" 100 ft 30 m
850
4" 4" 40 ft 12 m
6" 6" 100 ft 30 m
Installations in the U.S. require exhaust vent pipe that is a combination of PVC & CPVC complying with ANSI/ASTM D1785
F441, polypropylene pipe that complies with ULC S636, or stainless steel complying with UL1738. Installations in Canada
requireexhaustventpipethatiscertiedtoULCS636.
Intake (air) pipe may be ABS, PVC, CPVC or galvanized material.
Installer must comply fully with manufacturer's installation instructions, including use of minimum exhaust length CPVC, to
maintainANSIZ21.13safetycertication.
Closet and alcove installations do not allow the use of PVC under any circumstances
* To calculate max equivalent length, measure the linear feet of the pipe, and add 5 feet (1.5m) for each elbow used.
**
Allowed only if the vent pipe is no more than 20 equivalent feet longer than the air pipe.
** **
Waterowswitch(285only)
Low water cutoff
0 - 10V convertor for
modulation control
High & Low gas pressure
switches
Boiler pump (285-500)
Concentric vent terminal, 2"
Concentric vent terminal, 3"
Flush-mount terminal, 3"
Flush-mount terminal, 4"
Propane conversion kit
Condensate neutralizer kit
BACnet gateway
LON gateway
BNTV
BNTV
BNTV
BNTV
BNTV
BNTV
BNTV
BNTV