Submittal
Sizing Data
Accessories
Side-wallventterminalforindoorinstallation(requiredforside-wallventing)
Side-wallcombustionairterminalforindoorinstallation(required only for ducted combustion air)
Outdoor vent terminal and combustion air terminal
NOTES:
1. Inputandoutputmustbederated4%per1000feetabovesealevelwheninstalledabove2000feetaltitude.
2. Dimensionsarenominal.
3. Forotherboilerratings:
BoilerHorsepower:HP=Output RadiationSurface:EDRsq.ft.= Output
33,475 150
Water Flow
Data
MT2H (Boiler)
TEMPERATURE RISE
20°F 11°C 25°F 14°C 30°F 17°C 35°F 19°C
Flow H/L Flow H/L Flow H/L Flow H/L Flow H/L Flow H/L Flow H/L Flow H/L
Size gpm feet lpm m gpm feet lpm m gpm feet lpm m gpm feet lpm m
400 34 6.3 129 1.9 27 4.0 102 1.2 23 2.8 87 0.9 19 2.1 72 0.6
MT2V (Water Heater)
HARD WATER NORMAL WATER SOFT WATER
Flow H/L Temp Flow H/L Temp Flow H/L Temp Flow H/L Temp Flow H/L Temp Flow H/L Temp
Size gpm feet rise °F lpm m rise °C gpm feet rise °F lpm m rise °C gpm feet rise °F lpm m rise °C
200 45 7.3 8 170 2.2 4 35 4.4 10 133 1.3 6 23 1.9 15 87 0.6 8
300 45 7.4 11 170 2.3 6 35 4.5 15 133 1.4 8 23 2.0 22 87 0.6 12
400 45 7.4 15 170 2.3 8 35 4.5 19 133 1.4 11 23 2.0 30 87 0.6 17
Thermal Gas Conn.Water
eziS .nnoCeziSycneiciffEledoM
BTU/h kW BTU/h kW %NPT NPT lbs kg
MT2H0400 399,000 116.9 340,000 99.6 85.3 3/41-1/2 330 150
MT2V0200 199,900 58.6 169,915 49.8 85 270 123
MT2V0300 300,000 87.9 255,000 74.7 85 300 136
MT2V0400 400,000 117.2 339,915 99.6 85 330 150
gnippihStuptuOtupnI
Weight
3/41-1/2
3/41-1/2
3/41-1/2
Thermal Gas Conn.Water
eziS .nnoCeziSycneiciffEledoM
BTU/h kW BTU/h kW %NPT NPT lbs kg
MT2H0400 399,000 116.9 340,000 99.6 85.3 3/41-1/2 330 150
MT2V0200 199,900 58.6 169,915 49.8 85 270 123
MT2V0300 300,000 87.9 255,000 74.7 85 300 136
MT2V0400 400,000 117.2 339,915 99.6 85 330 150
gnippihStuptuOtupnI
Weight
3/41-1/2
3/41-1/2
3/41-1/2
BMT2H
BMT2V
BMT2H0400
BMT2V0200
BMT2V0300
BMT2V0400