Installation / Operation Instruction Manual
Page 33
Brute Deluxe (200, 300, 400), Install & Operating
6.G Shutting Down the Brute Deluxe
1. Switch o the main electrical disconnect switch.
2. Close all manual gas valves.
3. If freezing is anticipated, drain the Brute Deluxe
and be sure to also protect building piping from
freezing.
This step to be performed by a qualied
service person.
6.H To Restart the Brute Deluxe
If drained, follow Section 6.1 in this manual for proper
lling and purging.
1. Switch o the main electrical disconnect switch.
2. Close all manual gas valves.
3. WAIT FIVE (5) MINUTES.
4. Set the aquastat or thermostat to its lowest
setting.
5. Open all manual gas valves.
6. Reset all safety switches (pressure switch, manual
reset high limit, etc.).
7. Set the temperature controller to the desired
temperature setting and switch on electrical
power.
8. Burner will go through a pre-purge period and
ignitor warm-up period, followed by ignition.
SECTION 7 Maintenance
7.A System Maintenance
1. Lubricate the system water-circulating pump, if
required, per the instructions on the pump.
2. If a strainer is employed in a pressure reducing
valve or the piping, clean it every six months.
3. Inspect the venting system for obstruction or
leakage at least once a year. Periodically clean
the screens in the vent terminal and combustion
air terminal (when used).
4. Keep the appliance area clear and free from
combustible materials, gasoline, and other
ammable vapors and liquids.
5. If the appliance is not going to be used for
extended periods in locations where freezing
normally occurs, it should be isolated from the
system and completely drained of all water. All
systems connected to it should also be drained or
protected from freezing.
6. Low water cutos, when installed on a
residential hot water heating system, the probe
should be removed and cleaned every ve years.
When installed on a commercial application, the
probe should be removed and cleaned annually.
7. The Pressure Relief Valve should be inspected
and tested every year.
8. Inspect ue passages, and clean with brushes/
vacuums, if necessary. Sooting in ue passages
indicates improper combustion. Determine the
cause and correct.
9. Inspect the vent system and air intake system,
and if the vent system is Category III, ensure
that all joints are sealed properly. If joints need
to be resealed, follow venting manufacturer's
instructions to clean and reseal vent system.
7.B Appliance Maintenance and
Component Description
Only genuine Bradford White replacement parts should
be used.
Caution
Label all wires prior to disconnection when
servicing controls. Wiring errors can cause
improper and dangerous operation. Verify proper
operation after servicing.
Attention
Lors d’entretien ou de réparation des commandes,
étiquetez tous les câbles avant de les déconnecter.
Des erreurs de câblage peuvent provoquer des
fonctionnements incorrects et dangereux. Après
toute intervention d’entretien ou de réparation,
vérifier que l’appareil fonctionne correctement.